Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ALPHA PRECISION GROUP. LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ALPHA PRECISION GROUP. LLC in 95 MASON RUN ROAD, RIDGWAY, PA 15853 (NAICS 332117). OSHA activity number 347376592.

Watch Alpha Precision Group. LLC — free Get an email when a new federal OSHA severe-injury report for Alpha Precision Group. LLC is published. One employer, no account, unsubscribe in one click.
Site address
95 MASON RUN ROAD
City
RIDGWAY
State
PA
ZIP
15853
Mailing
95 MASON RUN ROAD, RIDGWAY, PA 15853
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332117
Employees
153
Ownership type
A

9 citations on file for this inspection.

1910.106 E06 II

Serious Gravity 5 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $10578.00 · Current $10000.00 Reduced
29 CFR  1910.106(e)(6)(ii): 29 CFR 1910.106(e)(6)(ii): Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 & less degree F (37.8  or less degree C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected:   a)  Alpha Precision Group, LLC, Kohler Room - On or about 3/27/24, and times prior thereto:  Employees utilized an approximately 5 gallon plastic container to transfer Rustproofing Oil (category 3 flammable liquid) to the 200 gallon dip tank.  The approximately 5 gallon container was not bonded to provide the dissipation of static electricity associated with dispensing the flammable liquid from the  5 gallon container to the dip tank.  b) Alpha Precision Group, LLC, Kohler Room - On or about 3/27/24, and times prior thereto:  Employees utilized an approximately 5 gallon plastic container to transfer Rustproofing Oil (category 3 flammable liquid) from the larger drum.  The 5 gallon container was not bonded to provide the dissipation of static electricity associated with dispensing the  flammable liquid from the 5 gallon plastic container to into the dip tank.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $10000
  • — Z (S) $10578

1910.215 B09

Other-than-serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $5288.00 · Current $4000.00 Reduced
29 CFR  1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:  a.) Alpha Precision Group, LLC dba Alpha Sintered Metals, die setter area - on or about 3/27/24 and times prior thereto: The tongue guard for the left grinding wheel on the Baldor bench grinder  (serial #B150126136) was positioned 1 inch away from the grinding wheel.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $4000
  • — Z (S) $5288

1910.307 C

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $10578.00 · Current $10000.00 Reduced
29 CFR  1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location (Reference 1910.125(e)(1)(i)):    a.) Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about 3/27/24 and at times prior thereto: A 110v electrical disconnect was located above the Kohler Rustproofing oil dip tank. The disconnect was not listed and labeled to be used in a potentially flammable environments.  b.) Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about 3/27/24 and at times prior thereto: An outlet was located in the Kohler Rustproofing dip tank enclosure.  The outlet was not Class 1, Division 1 to be located in the area of the dip tank.  c.)  Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about 3/27/24 and at times prior thereto:  A relocatable power tap was located on a ledge of the Kohler Rustproofing dip tank enclosure.  The power tap was not approved for flammable locations.  d.)  Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about  3/27/24 and at times prior thereto: A precision position gauge was located near the Kohler Rustproofing dip tank.  The gauge was was not approved for flammable locations   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $10000
  • — Z (S) $10578

1910.124 B04 II

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.124(b)(4)(ii): Mechanical ventilation did not conform to NFPA 34-1995, Standard for Dip Tanks Containing Flammable or Combustible Liquids Section 7.7:   a.) Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about 3/27/24 and at times prior thereto: A section of the ventilation duct work inside the enclosure was constructed of a flexible plastic section. All equipment for removing flammable vapors must be from steel construction in accordance with NFPA 34.   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Other-than-serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $7052.00 · Current $0.00 Reduced
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a.) Alpha Precision Group, LLC dba Alpha Sintered Metals; under stairs by office door - on or about 03/27/24 and times prior thereto: The area in front of 480 electrical panel box and a disconnect was being used for storage. A cart and cardboard boxes  were staged within 2 feet of both the electrical panel and disconnect.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $0
  • — Z (S) $7052

1910.305 G02 II

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $10578.00 · Current $0.00 Reduced
29 CFR  1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:    a.) Alpha Precision Group, LLC dba Alpha Sintered Metals -  on or about 03/27/24 and times prior thereto: equipment including but not limited to, an electrical power box power cord was spliced into a a surge protector extension cord.  The surge protector had another flexible extension cord that plugged into the position gauge for power.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $10578

1910.1200 H01

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $7052.00 · Current $0.00 Reduced
29 CFR  1910.1200(h)(1):Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:  a) Alpha Precision Group, LLC dba Alpha Sintered Metals - on 3/27/24 and times prior thereto:  Employees worked with and around hazardous substances including, but not limited to, RP150 Rustproofing oil during work operations onsite.  The employer did not provide hazard communication training for all employees who worked with and around hazardous substances.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7052

1910.124 J01 I

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.124(j)(1)(i): Hoods and ductwork of the ventilation system were not inspected for corrosion or damage at least quarterly during operation:    a.) Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about 3/27/24 and at times prior thereto: Regular testing and inspections of the ventilation system were not being conducted to ensure equipment was operating properly and no hazardous conditions existed.  The  company inspected the ventilation as an annual preventative maintenance task instead of a quarterly inspection.   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.124 J02 I

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.124(j)(2)(i): The employer did not ensure airflow was adequate at least quarterly during operation:   a.) Alpha Precision Group, LLC dba Alpha Sintered Metals, Kohler room, on or about 3/27/24 and at times prior thereto: Regular testing and inspections of the ventilation system were not being conducted to ensure equipment was operating properly and no hazardous conditions existed.   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347376592.