MOOSIC, PA —
OSHA Inspection: NUTRITION CORP.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of NUTRITION CORP. in 4135 BIRNEY AVENUE, MOOSIC, PA 18507 (NAICS 311991). OSHA activity number 347404733.
Where did this inspection happen?
- Establishment
- NUTRITION CORP.
- Site address
- 4135 BIRNEY AVENUE
- City
- MOOSIC
- State
- PA
- ZIP
- 18507
- Mailing
- 4135 BIRNEY AVENUE, MOOSIC, PA 18507
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311991
- Employees
- 164
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01
- Issued
- Penalty
- Initial $8296.00 · Current $6650.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Waste Area- On or about April 9, 2024, employees were exposed to fire hazards from electrical panels that did not have sufficient access to allow ready and safe operation. CORRECTED DURING INSPECTION
Recent events (2)
- — I (S) $6650
- — Z (S) $8296
1910.303 B02
- Issued
- Abate by
- Penalty
- Initial $10372.00 · Current $8350.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Panel LP-4- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel that was not installed utilizing the manufacturer's panel dead-front mounting instructions. b) Panel LP-6- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel that was not installed utilizing the manufacturer's panel dead-front mounting instructions. c) Panel PP-2- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel that was not installed utilizing the manufacturer's panel dead-front mounting instructions. d) Panel PP- 3- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel that was not installed utilizing the proper dead-front panel and the mounting instructions. e) Panel PP-4- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel that was not installed utilizing the proper dead-front panel and the mounting instructions. f) Panel PP-7- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel that was not installed utilizing the manufacturer's panel dead-front mounting instructions and an altered dead front latching system. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $8350
- — Z (S) $10372
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Electrical Panel PP-3- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel with the dead-front cover not properly enclosing the live parts of the electrical panel. b) Electrical Panel PP-4- On or about April 9, 2024, employees were exposed to electrical shock from an electrical panel with the dead-front cover not properly enclosing the live parts of the electrical panel. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at NUTRITION CORP.
MOOSIC, PA—2024-04-15 00:00:00
NUTRITION CORP.
View NUTRITION CORP.'s full OSHA safety record →
More inspections in this industry (NAICS 311991)
TORRANCE, CA—2026-07-01
SHINE DUMPLINGS INC.
TORRANCE, CA—2026-07-01
CORTECH WEST STAFFING LLC
HILLSBORO, OR—2026-06-30
317744560 - RESER'S FINE FOODS INC
OXNARD, CA—2026-06-29
BOSKOVICH FARMS, INC.
EUGENE, OR—2026-06-10
317744480 - MARY ELLENS SALADS LLC
More inspections in PA
MILTON, PA—2026-07-10
HOMETOWN FOODS CHEF BOYARDEE CO.