Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: NEW ENGLAND EXPERT TECHNOLOGIES CORP. - WINDSOR

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NEW ENGLAND EXPERT TECHNOLOGIES CORP. - WINDSOR in 545 MARSHAL PHELPS ROAD, WINDSOR, CT 06095 (NAICS 332721). OSHA activity number 347438475.

Watch NEW England Expert Technologies Corp. - Windsor — free Get an email when a new federal OSHA severe-injury report for NEW England Expert Technologies Corp. - Windsor is published. One employer, no account, unsubscribe in one click.
Site address
545 MARSHAL PHELPS ROAD
City
WINDSOR
State
CT
ZIP
06095
Mailing
545 MARSHAL PHELPS ROAD, WINDSOR, CT 06095
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332721
Employees
52
Ownership type
A

8 citations on file for this inspection.

1910.303 B02

Other-than-serious Gravity 1 2 instances 8 exposed
Issued
Penalty
Initial $3496.00 · Current $3000.00 Reduced
29 CFR  1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On, or about, April 25, 2024, in the following locations, relocatable power taps were energized through extension cords, which is not in accordance with the listing/labelling for relocatable power taps:  A.	Production Area, East Side Exterior Wall, near Machine #156:  Inspection workstation. B.	CMM:  Recently relocated inspection machine.
Recent events (2)
  • — I (O) $3000
  • — Z (S) $3496

1910.305 G01 IV A

Other-than-serious Gravity 1 3 instances 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(A):  Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On, or about, April 25, 2024, in the following locations, extension cords were used in lieu of permanent wiring: A.	Production Area, East Side Exterior Wall, near Machine #156:  Inspection workstation. B.	Shipping:  Shipping scale. C.	CMM:  A recently located inspection/testing machine.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6857.00 · Current $4000.00 Reduced
29 CFR  1910.332(b)(1):  Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  Company:  On, or about, May 13, 2024, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing live trouble-shooting and when verifying whether or not electrical equipment was properly de-energized.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $6857

1910.335 A01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.335(a)(1)(i):  Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  Company:  On, or about, May 13, 2024, personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.215 B09

Other-than-serious 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.215(b)(9):  The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:  Maintenance Shop:  On, or about, April 25, 2024, the tongue guard provided on the JET bench mounted grinder was measured to be one half of an inch from the abrasive wheel.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 I C

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(1)(i)(C):  For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work pace was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303.  Other equipment associated with the electrical installation and located above or below the electric equipment extended more than 153 mm (6 in.) beyond the front of the electric equipment:  Shipping Area:  On, or about, April 25, 2024, a General Electric transformer was located in the working space for a Murray Load Center electrical panel.  The transformer projected 17 inches from the face of the Load Center enclosure.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 II

Other-than-serious 1 instance 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  Wall behind DMU 50:  On, or about, April 25, 2024, electrical tape was used to cover openings in a General Electric 'A' series panelboard at positions 25, 27 and 29.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 E01 II

Other-than-serious 1 instance 50 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.1200(e)(1)(ii):  The written hazard communication program did not include the methods the employer would use to inform employees of the hazards of non-routine tasks, and the hazards associated with chemicals contained in unlabeled pipes in their work areas:  Company:  On, or about, May 13, 2024, the employer's written Hazard Communication Program did not address non-routine tasks.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347438475.