OSHA Inspection: E&S ELECTRICAL CORP

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of E&S ELECTRICAL CORP in 132 W 14TH STREET, NEW YORK, NY 10011 (NAICS 238210). OSHA activity number 347472532.

Watch E&S Electrical Corp — free Get an email when a new federal OSHA severe-injury report for E&S Electrical Corp is published. One employer, no account, unsubscribe in one click.
Establishment
E&S ELECTRICAL CORP
Site address
132 W 14TH STREET
City
NEW YORK
State
NY
ZIP
10011
Mailing
59-96 GRAND AVENUE, FLUSHING, NY 11378
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
238210
Employees
4
Ownership type
A

3 citations on file for this inspection.

1926.405 G02 V

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $4839.00 · Current $4839.00
29 CFR  1926.405(g)(2)(v): Flexible cords and cables were not protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures:  Location:  a) Cellar of the building, 132 West 14th Street, New York, NY 10011  On or about April 24th, 2024, employees were exposed to electrical hazards. The incoming feeding cable entered the breaker panel was not protected from abrasion by using a busing or fitting at the entrance.
Recent events (2)
  • — C (S) $4839
  • — Z (S) $4839

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Penalty
Initial $4839.00 · Current $4839.00
29 CFR  1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work:  Location:  a) Cellar of the building, 132 West 14th Street, New York, NY 10011  On or about April 24th, 2024, two employees were running 2BX cables from the elevator shelf on the 8th floor to the cellar to be connected to the energized 3-phase 480-V electrical panel. Employees were not protected against electric shock by de-energizing the panels or wearing personal protective equipment with insulation.
Recent events (2)
  • — C (S) $4839
  • — Z (S) $4839

1904.39 A02

Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $3457.00 · Current $3457.00
29 CFR  1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye.  Location:  a) Cellar of the building, 132 West 14th Street, New York, NY 10011  On or about April 24th, 2024, the employer did not report within 24 hours a work-related incident in which an employee suffered from electrical shocks and burns and was hospitalized for injuries. The incident occurred on 04/24/2024, and OSHA was notified on 05/08/2024.
Recent events (2)
  • — C (O) $3457
  • — Z (O) $3457