Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WEST BROADWAY DISTRIBUTION SERVICES, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WEST BROADWAY DISTRIBUTION SERVICES, LLC in 3000 7TH AVENUE, ALTOONA, PA 16602 (NAICS 493110). OSHA activity number 347557035.

Watch West Broadway Distribution Services, LLC — free Get an email when a new federal OSHA severe-injury report for West Broadway Distribution Services, LLC is published. One employer, no account, unsubscribe in one click.
Site address
3000 7TH AVENUE
City
ALTOONA
State
PA
ZIP
16602
Mailing
3000 7TH AVENUE, ALTOONA, PA 16602
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
34
Ownership type
A

7 citations on file for this inspection.

1910.303 B02

Serious Gravity 10 2 instances 2 exposed
Issued
Penalty
Initial $11292.00 · Current $6100.00 Reduced
29 CFR  1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a) Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, an electrical outlet box (110 volt) being used to supply power to a portable fan (white) on the Sticker Stock table was being used as a pendant style device.  The outlet box was laying on plastic that was covering a stack of books on the floor behind the Sticker Stock table.   The outlet box lacked proper strain relief to be used as a pendant style device and was equipped with knockouts that could be displaced by an employee's fingers during use.  Employees using the outlet box were exposed to the hazard of electrical shock.  b) Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, an electrical outlet box (110 volt) being used to supply power to a portable black fan (black) at the Sticker Stock table was being used as a pendant style device.  The outlet box was laying on the floor behind the Sticker Stock table.  The outlet box lacked proper strain relief to be used as a pendant style device and was equipped with knockouts that could be displaced by an employee's fingers during use.  Employees using the outlet box were exposed to the hazard of electrical shock.
Recent events (2)
  • — I (S) $6100
  • — Z (S) $11292

1910.303 B07 IV

Serious Gravity 10 2 instances 2 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(iv):  There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    a) Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, an electrical cord that supplied power (110-volt) to both a white portable fan and a black portable fan on the Sticker Stock tables was badly damaged with large sections of the outer cover worn away and no strain relief where the cord entered each outlet box.  Employees using the outlet boxes in Sticker Stock area were exposed to the hazards of electrical shock and electrocution.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 4 instances 34 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(2)(i):  Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures:      a)  Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, an electrical outlet (110 Volt) located near the employee restrooms was not equipped with a cover.  The outlet was being used to provide power to a ULine brand potable fan.  The missing outlet box cover exposed employees working in the area to hazard of electric shock.      b)  Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, a junction box located near the bottom of the stairs near the fire suppression system was not equipped with a cover.  Employees working in the area where exposed to the hazard of electric shock due to the missing junction box cover.    c)  Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, a junction box (110 Volt) mounted on a building column to the right of where the Sticker Stock table fans were plugged in was not equipped with a cover.  The missing junction box cover exposed employees working in the area to hazard of electric shock.      d)  Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:   Observed on or about June 11, 2024, conduit leading into a junction box that was mounted above a row of storage racks in the main warehouse had separated from the junction box exposing the conductors housed within the conduit.  The separated conduit exposed employees working in the area to hazard of electric shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 2 instances 34 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A):  Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a) Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, a flexible cord (110 Volt) used to supply power to a Frigidaire brand portable air conditioning system located inside the main office area was being used as a substitute for the fixed wiring of the structure.  The flexible cord was wrapped around the outlet it was plugged in to, tied around a building beam above the outlet, and ran through an office window.  b) Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, a black flexible cord (110 Volt) was wrapped around a pipe and draped over the corner of the main office roof.  The black flexible cord was used to supply power to a white portable fan on the sticker stock table.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 1 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(C):  Flexible cords and cables were used where run through doorways, windows, or similar openings:    a)  Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, an orange flexible cord (110-volt) was run from an outlet in the warehouse area through a main office window.  The flexible cord was being used to provide power to a Frigidaire brand portable air conditioning system located inside the main office.  Running a flexible cable through window opening could result in wear on the cord which could create fire and electric shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.40 A

Other-than-serious 1 instance 34 exposed
Issued
Abate by
Penalty
Initial $1613.00 · Current $900.00 Reduced
29 CFR 1904.40(a):  The employer did not provide an authorized government representative the records within the four business hours:    a) Jobsite, 3000 7th Avenue, Altoona, PA 16602:  On or about July 17, 2024, the employer did not provide OSHA a copy of their OSHA 300 injury and illness logs within 4 business hours.   The records were requested  as part of a document request that was sent to the employer on the afternoon of July 17, 2024.  The requested records were never received by OSHA.
Recent events (2)
  • — I (O) $900
  • — Z (O) $1613

1910.37 B02

Other-than-serious 1 instance 34 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   a)  Warehouse Area, 3000 7th Avenue, Altoona, PA 16602:  Observed on or about June 11, 2024, an exit door located to the left of the employee restroom was not marked by a sign reading "Exit."  The exit door led to a parking area outside of the building.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

SPEEDX