MADISON, WI —
OSHA Inspection: DISTRICT COUNCIL OF MADISON, INC. SOCIETY OF ST. VINCENT DE PAUL
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DISTRICT COUNCIL OF MADISON, INC. SOCIETY OF ST. VINCENT DE PAUL in 1109 JONATHON DRIVE, MADISON, WI 53713 (NAICS 453310). OSHA activity number 347590267.
Where did this inspection happen?
- Site address
- 1109 JONATHON DRIVE
- City
- MADISON
- State
- WI
- ZIP
- 53713
- Mailing
- 2033 FISH HATCHERY RD P.O. BOX 259686, MADISON, WI 53725
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 453310
- Employees
- 70
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C04 I
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $16131.00
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) On or about and times prior to June 28, 2024, hazardous energy control procedures were not utilized for the Hytrol Model TH Conveyor System to protect employees from the unexpected startup during maintenance and servicing activities such as unjamming. b) On or about and throughout June 1, 2024, to June 27, 2024, hazardous energy control procedures were not utilized for the Hytrol Model TH Conveyor to protect employees from unexpected startup during maintenance and servicing activities such as unjamming.
Recent events (2)
- — C (S) $16131
- — Z (S) $16131
1910.147 C07 I A
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $16131.00
General-duty citation text
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation: On or about July 1, 2024, the employer failed to provide authorized Lockout/Tagout training to maintenance personnel engaged in maintenance and servicing activities such as unjamming or dismantling of equipment.
Recent events (2)
- — C (S) $16131
- — Z (S) $16131
1910.147 C07 I A
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $16131.00
General-duty citation text
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation. On or about June 17, 2024, through June 24, 2024, in the clothing room's conveyor line, line workers were not provided with authorized Lockout/Tagout training and were exposed to caught-in hazards while addressing clothing jams on the Hytrol Conveyor Model TH's tail end pulley and or snub roller.
Recent events (2)
- — C (S) $16131
- — Z (S) $16131
1910.147 C07 I A
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $16131.00
General-duty citation text
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation a) On or about June 28, 2024, in the clothing room's conveyor line supervisors were not provided with authorized Lockout/Tagout training and were exposed to caught-in hazards while addressing clothing jams on the tail end pulley and or snub roller of Hytrol Conveyor Model TH. b) On or about June 1, 2024, through June 27, 2024, in the clothing room's conveyor line, supervisors were not provided with Authorized Lockout/Tagout Training and were exposed to caught-in hazards while addressing clothing jams on the tail end pulley and or snub roller of Hytrol Conveyor Model TH.
Recent events (2)
- — C (S) $16131
- — Z (S) $16131
1910.147 C07 I B
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $16131.00
General-duty citation text
29 CFR 1910.147(c)(7)(i)(B): Affected employees were not instructed in the purpose and use of the energy control procedure: On or about and times prior to July 1, 2024, the employer failed to provide affected level training to clothing line employees while authorized personnel engaged in maintenance and servicing activities on the Hytrol Model TH Conveyor system.
Recent events (2)
- — C (S) $16131
- — Z (S) $16131
1910.212 A01
- Issued
- Penalty
- Initial $16131.00 · Current $16131.00
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about July 1, 2024, one or more methods of machine guarding was not provided to protect clothing line employees from a caught-in hazard created by the Hytrol Model TH (S/N:16DZ65) conveyor system tail end pulley and snub roller. Employees were not protected against operational necessity or inadvertent contact with the zone of danger associated with the discharge end of the conveyor.
Recent events (2)
- — C (S) $16131
- — Z (S) $16131
1910.303 B07 I
- Issued
- Penalty
- Initial $11524.00 · Current $11524.00
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. On or about and times prior to July 1, 2024, employees stationed near the variable speed controls of the Hytrol Model TH conveyor (S/N:16DZ64) were exposed to an electrical hazard due to unused openings in the gang box.
Recent events (2)
- — C (S) $11524
- — Z (S) $11524
1910.303 G01
- Issued
- Penalty
- Initial $6913.00 · Current $6913.00
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about and times prior to August 19, 2024, the electrical panel to the bailer was not maintained clear to allow for sufficient access.
Recent events (2)
- — C (S) $6913
- — Z (S) $6913
More inspections in this industry (NAICS 453310)
MERIDIAN, ID—2026-07-15
EASTER SEALS - GOODWILL NORTHERN ROCKY MOUNTAINS
BLOOMINGTON, IL—2026-07-14
ONCE UPON A CHILD
BRATTLEBORO, VT—2026-07-06
GOODWILL INDUSTRIES OF THE BERKSHIRE AND SOUTHERN VERMONT, INC.
SPOKANE, WA—2026-06-16
WA317991736 - GOODWILL INDUSTRIES OF THE INLAND NORTHWEST
PUYALLUP, WA—2026-06-16
WA317991646 - TVI INC
More inspections in WI
WAUSAU, WI—2026-07-16
MIRON CONSTRUCTION CO. INC.
ELROY, WI—2026-07-15
WABASH NATIONAL SERVICES, L.P.
SUSSEX, WI—2026-07-15
KINGS SUPERIOR CONSTRUCTION LLC
DELAVAN, WI—2026-07-15
TERONOMY BUILDERS, INC.
DELAVAN, WI—2026-07-15
A. GOMEZ CARPENTRY, INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347590267.