SCHUYLKILL HAVEN, PA —
OSHA Inspection: DFA DAIRY BRAND FLUID, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DFA DAIRY BRAND FLUID, LLC in 110 MANHEIM ROAD, SCHUYLKILL HAVEN, PA 17972 (NAICS 311511). OSHA activity number 347618340.
Where did this inspection happen?
- Establishment
- DFA DAIRY BRAND FLUID, LLC
- Site address
- 110 MANHEIM ROAD
- City
- SCHUYLKILL HAVEN
- State
- PA
- ZIP
- 17972
- Mailing
- 110 MANHEIM ROAD, SCHUYLKILL HAVEN, PA 17972
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311511
- Employees
- 120
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.22 A03
- Issued
- Abate by
- Penalty
- Initial $11524.00 · Current $11524.00
General-duty citation text
29 CFR 1910.22(a)(3): The employer did not ensure that walking-working surfaces are maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice: a) Case Handling: On or about July 15, 2024, employees were exposed to trip hazards while walking due to moving stack conveyor systems located on the walking working surface. b) Cheese Room: On or about July 15, 2024, employees were exposed to trip hazards while walking due to moving stack conveyor systems and the conveyors parts being mounted in the walking working surface. Abatement certification required.
Recent events (2)
- — I (O) $11524
- — Z (S) $11524
1910.36 G02
- Issued
- Abate by
- Penalty
- Initial $6913.00 · Current $6913.00
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points: a) Processing room: On or about July 15, 2024, employees were exposed to fire hazards due to the homogenizer and a wall mounted water hose reducing the exit access to the main hallway emergency exit door to 15 inches. b) Processing room: On or about July 15, 2024, employees were exposed to fire hazards due to a fixed ladder and flow control valves reducing the exit access to the main hallway emergency exit door less than 22 inches. c) Cold Loading Dock: On or about July 15, 2024, employees were exposed to fire hazards while working on the loading dock, due to the stack conveyor system blocking the designated emergency exit access because it was installed directly through a doorway opening. Abatement certification required.
Recent events (2)
- — I (O) $6913
- — Z (S) $6913
1910.212 A03 II
- Issued
- Abate by
- Penalty
- Initial $13828.00 · Current $13828.00
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle: a) Filling Room, NEP Machine: On or about July 15, 2024, employees were exposed to struck-by hazards due to the safety doors to the machine being left open while the machinery was operating. Abatement certification required.
Recent events (2)
- — I (O) $13828
- — Z (S) $13828
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $6913.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Processing room: On or about July 15, 2024, employees were exposed to shock hazards due to a yellow flexible cord being used to power a "Foam-It" doorway sanitizer for approximately 4 months. Abatement certification required.
Recent events (2)
- — I (S) $0
- — Z (S) $6913
1910.305 G01 IV D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $6913.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: a) Processing room: On or about July 15, 2024, employees were exposed to shock hazards due to a yellow flexible cord being attached with zip-ties to electrical conduit and pipe braces for approximately 4 months. 29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: b) Processing room: On or about July 15, 2024, employees were exposed to shock hazards due to a yellow flexible cord being used to power a "Foam-It" doorway sanitizer for approximately 4 months. Abatement certification required.
Recent events (2)
- — I (O) $6913
- — Z (S) $0
More inspections in this industry (NAICS 311511)
PLAINVIEW, MN—2026-07-08
111556 - PLAINVIEW MILK PRODUCTS COOPERATIVE
SUNNYSIDE, WA—2026-07-02
WA317991664 - DARIGOLD INC
ASHEVILLE, NC—2026-06-11
161352 - MILKCO,INC.
OGDEN, UT—2026-06-09
OATLY, INC.
DENVER, CO—2026-06-08
KROGER CO.
More inspections in PA
PHILADELPHIA, PA—2026-07-16
URUS CONSTRUCTION CORPORATION
JEFFERSON HILLS, PA—2026-07-16
MARATHON PETROLEUM COMPANY ASPHALT TERMINAL
SMITHFIELD, PA—2026-07-16
CARLISLE CONSTRUCTION MATERIALS
PITTSBURGH, PA—2026-07-15
DREAM GREENER LAWN & LANDSCAPE
COCHRANTON, PA—2026-07-15
CRAWFORD COUNTY HARDWOODS, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347618340.