NIAGARA, WI —
OSHA Inspection: NORTHBROOK LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of NORTHBROOK LLC in 1101 MILL STREET, NIAGARA, WI 54151 (NAICS 221111). OSHA activity number 347816845.
Where did this inspection happen?
- Establishment
- NORTHBROOK LLC
- Site address
- 1101 MILL STREET
- City
- NIAGARA
- State
- WI
- ZIP
- 54151
- Mailing
- 1101 MILL STREET, NIAGARA, WI 54151
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221111
- Employees
- 4
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.28 B01 I
- Issued
- Abate by
- Penalty
- Initial $9218.00 · Current $3750.00 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): Except as provided elsewhere in this section, the employer must ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by guardrail systems; safety net systems; or personal fall protection systems: On or about August 26, 2024, and thereafter, at a facility located at 1101 Mill Street in Niagara, WI; the employer did not ensure employees were protected from falls of greater than 4 feet into the pit around the #5 Generator. Employees walking past and working near the unprotected edge of the pit were exposed to falls of approximately 6.5 feet.
Recent events (3)
- — F (O) $3750
- — C (S) $9218
- — Z (S) $9218
1910.28 B11 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.28(b)(11)(i): Each employee exposed to an unprotected side or edge of a stairway landing that is 4 feet (1.2 m) or more above a lower level is protected by a guardrail or stair rail system: On or about August 26, 2024, at a facility located at 1101 Mill Street in Niagara, WI; employees exposed to a fall of greater than 4 feet to the lower level were not protected by a guardrail or stair rail system at the unprotected edge of the #3 Generator's Aisle bearing stairway landing. One side of the railing was not equipped with a top-rail or midrail and exposed employees to a fall of approximately 7 feet to the bottom the pit around the generator.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.28 B02 II
- Issued
- Abate by
- Penalty
- Initial $16131.00 · Current $3750.00 Reduced
General-duty citation text
29 CFR 1910.28(b)(2)(ii): In a hoist area when any portion of a guardrail system, gate, or chains is removed, and an employee must lean through or over the edge of the access opening to facilitate hoisting, the employee is protected from falling by a personal fall arrest system: At a facility located at 1101 Mill Street in Niagara, WI: a) On or about August 27, 2024; employees installing dewatering gates with the overhead hoist worked at and leaned over the edge of the hoist area where the guardrail system had been removed. Employees were not protected from falls into the intake reservoir (pond) while they facilitated hoisting of the dewatering gates. The draining pond had a water depth of approximately 10 feet. b) On or about August 28, 2024; employees removing the dewatering gates with the overhead hoist worked at and leaned over the edge of the hoist area where the guardrail system had been removed. Employees were not protected from falls into the empty pond while they facilitated hoisting of the dewatering gates. The empty pond created an approximate 10-foot fall to the lower level.
Recent events (3)
- — F (O) $3750
- — C (S) $16131
- — Z (S) $16131
1910.212 A01
- Issued
- Abate by
- Penalty
- Initial $11524.00 · Current $3750.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices, electronic safety devices, etc.: On or about October 17, 2024, at a facility located at 1101 Mill Street in Niagara, WI; the employer did not provide machine guarding to protect Plant Operator employees from the rotating parts of the Generators. a) At the #5 Generator, employees were exposed to the rotating Rotor from the aisleway north of the Rotor. A standard guardrail present along the aisleway did not prevent employees from contacting the rotating part. The outer edge of the guardrail was at most 34 inches from the struck-by and entanglement hazards present by the Rotor. The guardrail contained a swing-gate which was not locked, secured, or interlocked and allowed access to the Rotor from its north and south sides. b) At #4 Generator, employees were exposed to the rotating Rotor on the south side of the Rotor. The standard guardrail around the generator contained a swing gate which was not locked, secured or interlocked and allowed access to the south side of the Rotor. Employees accessing this area were not protected from the struck-by and entanglement hazards presented by the Rotor.
Recent events (3)
- — F (O) $3750
- — C (S) $11524
- — Z (S) $11524
1910.219 C02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.219(c)(2)(i): All exposed parts of horizontal shafting seven (7) feet or less from floor or working platform, excepting runways used exclusively for oiling, or running adjustments, shall be protected by a stationary casing enclosing shafting completely or by a trough enclosing sides and top or sides and bottom of shafting as location requires: On or about October 17, 2024, at a facility located at 1101 Mill Street in Niagara, WI; the employer did not enclose or otherwise protect horizontal shafts on Generators 5, 4, 3 or 1, which were located less than 7 feet from the floor or working platforms. Plant Operator employees were exposed to entanglement hazards presented by the rotating shafts of each of the Generators' shafts located between the respective turbine enclosures to mid-bearing housings; and between their mid-bearing housings and the Rotor/Stator assembly while they inspected the equipment and check oil levels at the mid-bearing housings.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.269 D02 I
- Issued
- Abate by
- Penalty
- Initial $11524.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.269(d)(2)(i): The employer shall establish a program consisting of energy control procedures, employee training, and periodic inspections to ensure that, before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up, or release of stored energy could occur and cause injury, the machine or equipment is isolated from the energy source and rendered inoperative: On or about August 26, 2024; at a facility located at 1101 Mill Street in Niagara, WI; the employer did not establish a program consisting of energy control procedures, employee training, and periodic inspections when employees conducted an annual shutdown of the generators and turbines, and isolated the river from the hydroelectric power generation system where the unexpected energizing, start up, or release of stored energy could occur and cause injury.
Recent events (3)
- — F (S) $0
- — C (S) $11524
- — Z (S) $11524
1910.269 D02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $3750.00
General-duty citation text
29 CFR 1910.269(d)(2)(iii): Procedures shall be developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section: On or about August 26, 2024; at a facility located at 1101 Mill Street in Niagara, WI; employees conducted an annual shutdown of the generators and turbines and isolated the river from the hydroelectric power generation system; however, the employer had not developed an energy control procedure for locking out hydroelectric power generation equipment and for isolation of the river from the system.
Recent events (3)
- — F (O) $3750
- — C (S) $0
- — Z (S) $0
1910.269 D02 V
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(d)(2)(v): The employer shall conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the provisions of paragraph (d) of this section are being followed: On or about August 26, 2024; at a facility located at 1101 Mill Street in Niagara, WI; the employer had not conducted a periodic inspection of the energy control procedure at least annually to ensure that the procedures and the provisions of paragraph (d) were being followed when employees conducted an annual shutdown of the generators and turbines, and isolated the river from the hydroelectric power generation system.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.269 D02 VI
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(d)(2)(vi): The employer shall provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of energy controls are acquired by employees. The training shall include the requirements of this subdivisions [A] through [C]: On or about August 26, 2024; at a facility located at 1101 Mill Street in Niagara, WI; the employer had not provided training to ensure that the purpose and function of the energy control program were understood by employees. The employer did not provide training to ensure that employees quired the knowledge and skills required for the safe application, usage, and removal of energy controls when employees conducted an annual shutdown of the generators and turbines, and isolated the river from the hydroelectric power generation system.
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 221111)
UMATILLA, OR—2026-05-29
DEPT. OF DEFENSE - USACE
UMATILLA, OR—2026-05-29
US ARMY CORPS OF ENGINEERS MCNARY DAM
EVERETT, WA—2026-05-20
WA317991327 - PUBLIC UTILITY DIST #1 SNOHOMISH COUNTY
CRAIG, AK—2026-05-12
ALASKA POWER & TELEPHONE COMPANY
SULTAN, WA—2026-04-15
WA317990791 - PUBLIC UTILITY DIST #1 SNOHOMISH COUNTY
More inspections in WI
WAUSAU, WI—2026-07-16
MIRON CONSTRUCTION CO. INC.
ELROY, WI—2026-07-15
WABASH NATIONAL SERVICES, L.P.
SUSSEX, WI—2026-07-15
KINGS SUPERIOR CONSTRUCTION LLC
DELAVAN, WI—2026-07-15
TERONOMY BUILDERS, INC.
DELAVAN, WI—2026-07-15
A. GOMEZ CARPENTRY, INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347816845.