FRANKLIN, PA —
OSHA Inspection: SPECIALTY FABRICATION AND POWDER COATING, LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of SPECIALTY FABRICATION AND POWDER COATING, LLC in 455 ALLEGHENY BOULEVARD PO BOX 790, FRANKLIN, PA 16323 (NAICS 332322). OSHA activity number 347929374.
Where did this inspection happen?
- Establishment
- SPECIALTY FABRICATION AND POWDER COATING, LLC
- Site address
- 455 ALLEGHENY BOULEVARD PO BOX 790
- City
- FRANKLIN
- State
- PA
- ZIP
- 16323
- Mailing
- 455 ALLEGHENY BOULEVARD PO BOX 790, FRANKLIN, PA 16323
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332322
- Employees
- 60
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.151 C
- Issued
- Abate by
- Penalty
- Initial $6511.00 · Current $3000.00 Reduced
General-duty citation text
29 CFR 1910.151(c):Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a. Specialty Fabrication and Powder Coating, LLC, Wash Bay area, on or about December 10th, 2024 and times prior thereto: Employees worked with and around corrosive materials including, but not limited to Cal Prep 52C (Detergent). The plumbed emergency eyewash station in the Wash Bay area was not suitable for quick drenching/flushing of the eyes and/or face in that: 1. The plumbed eyewash was inspected monthly versus weekly. 2. Upon activation the eyewash unit contained high pressure water that could cause further damage to the eye if used in an emergency event. 3. The eyewash unit contained "hot" water which could cause further damage to the eye if used in an emergency event. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3000
- — Z (S) $6511
1910.303 B07
- Issued
- Abate by
- Penalty
- Initial $4884.00 · Current $3000.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner: a.) Specialty Fabrication and Powder Coating, LLC, spray booth room next to entry doorway, on or about December 10th, 2024, and times prior thereto: A flexible Metal-Clad Cable (MC) was used as a means of fixed wiring for a light on the floor in the area outside of the spray booth room. The MC cable was powering a light fixture and was not supported at 6-foot intervals nor was supported within 12 inches of the junction box. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3000
- — Z (S) $4884
1910.303 G01 II
- Issued
- Abate by
- Penalty
- Initial $4884.00 · Current $3000.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a.) Specialty Fabrication and Powder Coating, LLC, spray booth room, on or about December 10th, 2024, and times prior thereto: Items including, but not limited to, various ladders were stored directly in front of an electrical disconnect box. The electrical disconnect was listed with a title of "Air Handler and Economizer" and was a Cutler-Hammer brand Heavy-Duty Safety switch (30 Amp, 600 Volt A-C). ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3000
- — Z (S) $4884
1910.107 G07
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.107(g)(7): "No smoking" signs in large letters on contrasting color backgrounds were not conspicuously posted at all spraying areas: a) Specialty Fabrication and Powder Coating, LLC, spray booth room, on or about December 10th, 2024, and times prior thereto: Areas around the spray booth area, where various powdered metals were sprayed, did not contain "No smoking" signage. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at SPECIALTY FABRICATION AND POWDER COATING, LLC
FRANKLIN, PA—2011-11-10 00:00:00
SPECIALTY FABRICATION AND POWDER COATING, LLC
FRANKLIN, PA—2011-11-10 00:00:00
SPECIALTY FABRICATION AND POWDER COATING, LLC
FRANKLIN, PA—2008-10-21 00:00:00
SPECIALTY FABRICATION AND POWDER COATING, LLC
View SPECIALTY FABRICATION AND POWDER COATING, LLC's full OSHA safety record →
More inspections in this industry (NAICS 332322)
PERTH AMBOY, NJ—2026-07-16
ENGLERT INC.
BRIDGEPORT, WV—2026-07-14
MID ATLANTIC METALWORKS INC.
KISSIMMEE, FL—2026-07-14
JELD-WEN
CASTLE ROCK, CO—2026-07-10
MASTER MAGNETICS, INC.
PITTSBURG, KS—2026-07-09
PROGRESSIVE PRODUCTS INC
More inspections in PA
PHILADELPHIA, PA—2026-07-16
URUS CONSTRUCTION CORPORATION
JEFFERSON HILLS, PA—2026-07-16
MARATHON PETROLEUM COMPANY ASPHALT TERMINAL
SMITHFIELD, PA—2026-07-16
CARLISLE CONSTRUCTION MATERIALS
PITTSBURGH, PA—2026-07-15
DREAM GREENER LAWN & LANDSCAPE
COCHRANTON, PA—2026-07-15
CRAWFORD COUNTY HARDWOODS, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347929374.