PAGO PAGO, AS —
OSHA Inspection: MEE WON INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MEE WON INC in NUUULI VILLAGE BEHIND CHICKEN STORE, PAGO PAGO, AS 96799 (NAICS 423930). OSHA activity number 348074113.
Where did this inspection happen?
- Establishment
- MEE WON INC
- Site address
- NUUULI VILLAGE BEHIND CHICKEN STORE
- City
- PAGO PAGO
- State
- AS
- ZIP
- 96799
- Mailing
- P.O. BOX 247, PAGO PAGO, AS 96799
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423930
- Employees
- 7
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.178 L01 I
- Issued
- Penalty
- Initial $2837.00 · Current $1986.00 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer shall ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l). Warehouse: Two employees were not trained or certified to operate the two onsite forklifts. Employees were exposed to crushed by hazards.
Recent events (2)
- — I (S) $1985.9
- — Z (S) $2837
1910.303 G02 I
- Issued
- Penalty
- Initial $3015.00 · Current $2111.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): A) Back of operational warehouse by plasma cutter: An electrical panel box was uncovered and there was no dead front installed, exposing live wire. Employees were exposed to electrical hazards. B) Employee Break Area: An electrical box was uncovered and there was no dead front installed, exposing live wire. Employees were exposed to electrical hazards. C) Storage Warehouse, back wall: An electrical box was uncovered and there was live wire exposed. Employees were exposed to electrical hazards.
Recent events (2)
- — I (S) $2110.5
- — Z (S) $3015
1910.305 A02 IV B
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(a)(2)(iv)(B): Conductors shall be run as multiconductor cord or cable assemblies. However, if installed as permitted in paragraph (a)(2)(i)(C) of this section, and if accessible only to qualified persons, feeders may be run as single insulated conductors. A) Back of operational warehouse by plasma cutter: conductors were not sealed in conduit. Employees were exposed to electrical shock hazards. B) Employee Break Area: conductors were not sealed in conduit. Employees were exposed to electrical shock hazards. C) Storage Warehouse, back wall: conductors were not sealed in conduit. Employees were exposed to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 A03
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: Warehouse storing oil pallets: The emergency exit door was blocked by boxes of tiles. Employees were exposed to fire hazards, including smoke inhalation and burns.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.101 B
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: Compressed gas cylinder(s) were not properly supported to prevent them from being knocked over: In the middle of the operational warehouse, two gas cylinders, oxygen and acetylene, were connected to regulators and in use and not secured. Employees were exposed to struck by hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 C01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: Employee break area, by back entrance: an ABC fire extinguisher was not mounted. Employees were exposed to fire hazards, such as smoke inhalation and burns.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Storage warehouse, back wall: the access to the electrical panel box and emergency electrical shut-off was blocked with storage. Employees were exposed to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 I
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: Break area, back wall: Insulated conductors were unprotected coming out of a metal pipe in the wall. Employees were exposed to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. Operational warehouse, blue baling machine controls box: Two knockouts were missing. Employees were exposed to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 423930)
DETROIT, MI—2026-07-15
STRONG STEEL PRODUCTS, LLC
OGDEN, UT—2026-07-10
TEAR A PART AUTO RECYCLING
GARNER, NC—2026-07-09
161490 - CAROLINA METAL RECYCLERS, LLC
JOPLIN, MO—2026-07-07
SERVICE RECYCLING - NORTH PLANT
HOLBROOK, NY—2026-07-01
ARROW SCRAP CORPORATION
More inspections in AS
PAGO PAGO, AS—2026-04-15
FTK CORPORATION
PAGO PAGO, AS—2026-04-15
TMP MASONRY CONSTRUCTION
PAGO PAGO, AS—2026-04-14
NNT INC.
PAGO PAGO, AS—2026-04-14
TONY'S CONSTRUCTION
PAGO PAGO, AS—2026-04-13
STEVENSON TRUCKING CORPORATION
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348074113.