Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: JMS WIND ENERGY, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JMS WIND ENERGY, LLC in 10490 COUNTY ROAD 90 BLACK HOLLOW SUN 1, SEVERANCE, CO 80524 (NAICS 237130). OSHA activity number 348450685.

Watch JMS Wind Energy, LLC — free Get an email when a new federal OSHA severe-injury report for JMS Wind Energy, LLC is published. One employer, no account, unsubscribe in one click.
Site address
10490 COUNTY ROAD 90 BLACK HOLLOW SUN 1
City
SEVERANCE
State
CO
ZIP
80524
Mailing
8022 S RAINBOW BLVD SUITE 406, LAS VEGAS, NV 89139
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
237130
Employees
200
Ownership type
A

2 citations on file for this inspection.

1910.269 D02 III

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $14895.00 · Current $14895.00
29 CFR  1910.269(d)(2)(iii): Procedures shall be developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section:  a) On or about August 18, 2025, the exposing employer did not ensure employees and general contractor employees were protected from arc flash explosion hazards.  Technicians engaged in the group lockout of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) with general contractor employees, did not utilize the procedures used for the control of potentially hazardous electrical energy, prior to commencing maintenance activities.  This condition exposed employees to arc flash explosion hazards.
Recent events (2)
  • — C (S) $14895
  • — Z (S) $14895

1910.269 D06 VII

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $14895.00 · Current $14895.00
29 CFR 1910.269(d)(6)(vii): Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and deenergizing of the machine or equipment have been accomplished. If normally energized parts will be exposed to contact by an employee while the machine or equipment is deenergized, a test shall be performed to ensure that these parts are deenergized:  a) On or about August 18, 2025, the exposing employer did not ensure employees and general contractor employees were protected from arc flash explosion hazards.  Technicians engaged in the group lockout of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) with general contractor employees, did not verify that electrical energy had been de-energized, isolated, and verified, prior to commencing maintenance activities.  This condition exposed employees to arc flash explosion hazards.
Recent events (2)
  • — C (S) $14895
  • — Z (S) $14895

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348450685.