SEVERANCE, CO —
OSHA Inspection: JMS WIND ENERGY, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of JMS WIND ENERGY, LLC in 10490 COUNTY ROAD 90 BLACK HOLLOW SUN 1, SEVERANCE, CO 80524 (NAICS 237130). OSHA activity number 348450685.
Where did this inspection happen?
- Establishment
- JMS WIND ENERGY, LLC
- Site address
- 10490 COUNTY ROAD 90 BLACK HOLLOW SUN 1
- City
- SEVERANCE
- State
- CO
- ZIP
- 80524
- Mailing
- 8022 S RAINBOW BLVD SUITE 406, LAS VEGAS, NV 89139
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 200
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.269 D02 III
- Issued
- Abate by
- Penalty
- Initial $14895.00 · Current $14895.00
General-duty citation text
29 CFR 1910.269(d)(2)(iii): Procedures shall be developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section: a) On or about August 18, 2025, the exposing employer did not ensure employees and general contractor employees were protected from arc flash explosion hazards. Technicians engaged in the group lockout of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) with general contractor employees, did not utilize the procedures used for the control of potentially hazardous electrical energy, prior to commencing maintenance activities. This condition exposed employees to arc flash explosion hazards.
Recent events (2)
- — C (S) $14895
- — Z (S) $14895
1910.269 D06 VII
- Issued
- Abate by
- Penalty
- Initial $14895.00 · Current $14895.00
General-duty citation text
29 CFR 1910.269(d)(6)(vii): Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and deenergizing of the machine or equipment have been accomplished. If normally energized parts will be exposed to contact by an employee while the machine or equipment is deenergized, a test shall be performed to ensure that these parts are deenergized: a) On or about August 18, 2025, the exposing employer did not ensure employees and general contractor employees were protected from arc flash explosion hazards. Technicians engaged in the group lockout of the PCS 025 (SG4400UD-MV-US, Serial #T2520600152) with general contractor employees, did not verify that electrical energy had been de-energized, isolated, and verified, prior to commencing maintenance activities. This condition exposed employees to arc flash explosion hazards.
Recent events (2)
- — C (S) $14895
- — Z (S) $14895
More inspections in this industry (NAICS 237130)
TWINSBURG, OH—2026-07-14
ERVIN CABLE CONSTRUCTION, LLC
LEXINGTON, KY—2026-07-09
69310 - DAVIS H ELLIOT COMPANY INC
POUGHQUAG, NY—2026-07-09
MK SHARP LLC.
KENMORE, WA—2026-07-08
WA317991980 - CASCADE TOWER & RIGGING INC
HUBBARD, TX—2026-07-07
3B DOZER SERVICE LLC
More inspections in CO
BROOMFIELD, CO—2026-07-16
WAVELYNX TECHNOLOGIES LLC
COLORADO SPRINGS, CO—2026-07-15
ELMER CONTRACTOR LLC
SHERIDAN, CO—2026-07-15
JOHN'S COLLISION REPAIR, INC.
CENTENNIAL, CO—2026-07-15
BRAKES PLUS, INC
ENGLEWOOD, CO—2026-07-15
PCL CIVIL CONSTRUCTORS INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348450685.