Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: HOT ACTION SPORTSWEAR, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HOT ACTION SPORTSWEAR, INC. in 307 DIVISION AVENUE UNIT 12, ORMOND BEACH, FL 32174 (NAICS 323113). OSHA activity number 348493594.

Watch HOT Action Sportswear, INC. — free Get an email when a new federal OSHA severe-injury report for HOT Action Sportswear, INC. is published. One employer, no account, unsubscribe in one click.
Site address
307 DIVISION AVENUE UNIT 12
City
ORMOND BEACH
State
FL
ZIP
32174
Mailing
307 DIVISION AVENUE UNIT 12, ORMOND BEACH, FL 32174
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323113
Employees
27
Ownership type
A

6 citations on file for this inspection.

1910.303 G02 I B

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $8276.00 · Current $4962.00 Reduced
29 CFR  1910.303(g)(2)(i)(B): Except as elsewhere required or permitted by this standard, live parts of electrical equipment operating at 50 volts or more was not guarded by suitable permanent, substantial partitions or screens so arranged so that only qualified persons would have access to the space within reach of the live parts. Any openings in such partitions or screens were not so sized and located that persons were not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them:  a. Throughout the production area: On or about September 10, 2025 and at times prior, the employer exposed employees to electrical hazards, in that workers were allowed to walk and work around live parts of a Centurian Automatic Multicolor Textile Printer operating at 50 volts or more, and the employer did not guard the equipment by a form of approved enclosure.
Recent events (2)
  • — I (S) $4962
  • — Z (S) $8276

1910.305 A02 V C

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $8276.00 · Current $4962.00 Reduced
29 CFR  1910.305(a)(2)(v)(C): Branch-circuit conductors were laid on the floor:  a. Throughout the production area: On or about September 10, 2025 and at times prior, the employer exposed employees to electrical hazards, in that employees were allowed to walk and work over branch-circuit conductors laying on the floor.
Recent events (2)
  • — I (S) $4962
  • — Z (S) $8276

1910.305 B01 II

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   a. Throughout the production area: On or about September 10, 2025 and at times prior, the employer exposed employees to electrical hazards, in that employees were allowed to walk and work near unused openings in cabinets and boxes that were not effectively closed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a. Throughout the production area: On or about September 10, 2025 and at times prior, the employer exposed employees to electrical hazards, in that employees were allowed to walk and work near outlet boxes missing cover faceplate or fixtured canopy.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure:  a. Throughout the production area: On or about September 10, 2025 and at times prior, the employer exposed employees to electrical hazards, in that employees used flexible temporary cables as permanent wiring providing current to multiple equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows, or similar openings:  a. Throughout the production area: On or about September 10, 2025 and at times prior, the employer exposed employees to electrical hazards, in that employees used flexible cords which were run through openings in and out of the work area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0