Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: DEPT. HOMELAND SECURITY - CBP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPT. HOMELAND SECURITY - CBP in 150 N MARIPOSA ROAD, NOGALES, AZ 85621 (NAICS 922190). OSHA activity number 348700931.

Watch Dept. Homeland Security - CBP — free Get an email when a new federal OSHA severe-injury report for Dept. Homeland Security - CBP is published. One employer, no account, unsubscribe in one click.
Site address
150 N MARIPOSA ROAD
City
NOGALES
State
AZ
ZIP
85621
Mailing
9 N. GRAND AVENUE, NOGALES, AZ 85621
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922190
Employees
614
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.   Driver Watch Area: On or about January 21, 2026, a relocatable power tap was being used to power a 1500W heater and 1200 W microwave.
Recent events (1)
  • — Z (S) $0

1910.303 G02 II

Serious Gravity 5 2 instances 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage:  a) Loading Docks 18/19: On or about January 21th, 2026, 120 VAC adjustable articulating dock lights had exposed live wires.  b) Loading Docks 31/32: On or about January 21th, 2026, 120 VAC adjustable articulating dock lights had exposed live wires.
Recent events (1)
  • — Z (S) $0

1910.305 E02

Serious Gravity 1 2 instances 10 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures:  a) Loading Docks 20/21: On or about January 21, 2026, the weatherproof switch boxes to control the 120 VAC adjustable articulating dock lights had missing covers which prevent water intrusion.  b) Loading Docks 22/23: On or about January 21, 2026, the weatherproof switch boxes to control the 120 VAC adjustable articulating dock lights had missing covers which prevent water intrusion.
Recent events (1)
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348700931.