BOULDER CITY, NV —
OSHA Inspection: DEPT. OF INTERIOR - BOR
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEPT. OF INTERIOR - BOR in HOOVER DAM, BOULDER CITY, NV 89006 (NAICS 221111). OSHA activity number 348824913.
Where did this inspection happen?
- Establishment
- DEPT. OF INTERIOR - BOR
- Site address
- HOOVER DAM
- City
- BOULDER CITY
- State
- NV
- ZIP
- 89006
- Mailing
- PO BOX 60400, BOULDER CITY, NV 89006
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221111
- Employees
- 150
- Ownership type
- D
Citations
7 citations on file for this inspection.
19100022 A01
- Issued
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition. Tool Room: On or about March 17, 2026, employees worked and issues tools from a room that had working surfaces that were not maintained in a clean and orderly condition limiting egress access.
Recent events (1)
- — Z (S) $0
19100028 B01 I A
- Issued
- Abate by
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.28(b)(1)(i)(A): The employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level was protected from falling by a standard guardrail system. Cooling Tower Crows Nest, A1- A9 and N1-N8: Employees worked in various crows nests throughout the dam with unprotected sides that was 4 feet (1.2 m) or more above a lower level.
Recent events (1)
- — Z (S) $0
19100029 B11
- Issued
- Abate by
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.29(b)(11): The employer did not ensure that when guardrail systems are used around holes, they are installed on all unprotected sides or edges of the hole. Between Generator A-8 and A-9: Employees walked pass or near a hole that had a potential fall hazard greater than 4 feet with a guardrail system that was not installed on all sides or edges of the hole.
Recent events (1)
- — Z (S) $0
19100212 B
- Issued
- Abate by
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving: Building 223, Carpenter Shop: On or about March 17, 2026, employees used unstable equipment without being bolted to the ground. This was observed on the following machines: a) Dayton Drill Press b) JET Bandsaw
Recent events (1)
- — Z (S) $0
19100215 B09
- Issued
- Abate by
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: On and prior to March 17, 2026, employees used a Baldor and Dayton bench grinder with the distance between the abrasive wheel periphery(s) and the adjustable tongue exceeding the allowed 1/4 inch in the following locations. a) 3rd Floor Machine Shop b) Turbine Gallery, Cooling Ring A-9
Recent events (1)
- — Z (S) $0
19100303 G01 II
- Issued
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Carpenter Shop, Inside Dam: Employees stored handheld fluorescent lights, measuring wheel and 6 foot A-frame ladder in front of their electrical panels.
Recent events (1)
- — Z (S) $0
19100023 B10
- Issued
- Abate by
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(b)(10): The employer did not ensure that any ladder with structural or other defects as immediately tagged "Dangerous: Do Not Use" or with similar language in accordance with § 1910.145 and removed from service until repaired in accordance with § 1910.22(d), or replaced. Throughout Dam: On or about March, 17, 2026, employees used A-frame and extension ladders that were not appropriately labeled with markings or decals to identify their load limits when working.
Recent events (1)
- — Z (O) $0
More inspections at DEPT. OF INTERIOR - BOR
YUMA, AZ—2026-06-22
DEPT. OF INTERIOR - BOR
BOULDER CITY, NV—2026-03-17
DEPT. OF INTERIOR - BOR
BOULDER CITY, NV—2026-03-17
DEPT. OF INTERIOR - BOR
YAKIMA, WA—2025-07-30
DEPT. OF INTERIOR - BOR
YAKIMA, WA—2025-07-30
DEPT. OF INTERIOR - BOR
View DEPT. OF INTERIOR - BOR's full OSHA safety record →
More inspections in this industry (NAICS 221111)
UMATILLA, OR—2026-05-29
DEPT. OF DEFENSE - USACE
UMATILLA, OR—2026-05-29
US ARMY CORPS OF ENGINEERS MCNARY DAM
EVERETT, WA—2026-05-20
WA317991327 - PUBLIC UTILITY DIST #1 SNOHOMISH COUNTY
CRAIG, AK—2026-05-12
ALASKA POWER & TELEPHONE COMPANY
SULTAN, WA—2026-04-15
WA317990791 - PUBLIC UTILITY DIST #1 SNOHOMISH COUNTY
More inspections in NV
CARSON CITY, NV—2026-07-13
JIFFY AIR TOOL
HENDERSON, NV—2026-07-13
INTEGRITY ROOFING LLC
LAS VEGAS, NV—2026-07-13
THE BERKLEY LAS VEGAS
RENO, NV—2026-07-10
AMUNDSON ROOFING, INC.
LAS VEGAS, NV—2026-07-09
CENTENNIAL MMA, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348824913.