On , OSHA opened an accident-driven safety inspection of OGDEN MARTIN SYSTEMS OF LANCASTER, INCORPORATED in ROUTE 441, MARIETTA, PA 17547 (NAICS 000000). OSHA activity number 123185621.

Watch Ogden Martin Systems OF Lancaster, Incorporated — free Get an email when a new federal OSHA severe-injury report for Ogden Martin Systems OF Lancaster, Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
ROUTE 441
City
MARIETTA
State
PA
ZIP
17547
Mailing
P.O. BOX 350, BAINBRIDGE, PA 17502
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
45
Ownership type
A
Industry flags
Manufacturing safety.

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 18 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $5250.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to the hazard of an uncontrolled fire or explosion resulting
from damage to the
facility's electronic control equipment.  The employer failed to implement
a standard operating
procedure requiring shut down of each affected boiler unit under the
following circumstances:
When the electronic controls for the affected boiler unit are damaged or
otherwise compromised
such that they can no longer be used to effectively control the operation.
(a)Ogden Martin Systems of Lancaster - The employer continued operation of
a
boiler unit after the Bailey Net 90 computerized control system for said
unit had
been rendered ineffective for controlling the operation, exposing
employees to the
hazard of an uncontrolled fire or explosion.  This violation occurred on
July
28,
1995.
ABATEMENT NOTE:
Among other methods, one feasible and acceptable abatement method to
correct this
hazard is ensure that a standard operating procedure is implemented
requiring shut down
of each affected boiler unit when the electronic controls for the unit are
damaged or
otherwise compromised such that they can no longer be used to effectively
control the
operation.  The employer shall install a shutdown device or devices in the
control room
independent of the Bailey computerized control system which permits remote
shutdown
of the fuel feed and combustion aspects of the operation of each affected
boiler unit.r
Recent events (2)
  • — F (S) $5250.00
  • — Z (S) $7000.00

5(a)(1)

Serious Gravity 10 1 instance 18 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $5250.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees
in that employees
were exposed to the hazard of an uncontrolled fire or explosion resulting
from lightning damage
to the facility's electronic control equipment.  The employer failed to
install an adequate
grounding and lightning protection system to protect the facility's
electronic control equipment.
(a)Ogden Martin Systems of Lancaster - The employers failure to install an
adequate
grounding and lightning protection system to protect the facility's Bailey
Net 90
computerized control system exposed the employees to the hazard of an
uncontrolled fire or explosion.  This violation occurred on July 28, 1995.
ABATEMENT NOTE:
Among other methods, one feasible and acceptable abatement method to
correct this
hazard is to ensure that a grounding and lightning protection system is in
place sufficient
to protect the facility's electronic control equipment.  Such a system
must be designed
to address weather and other conditions to which the facility is known to
be exposed.