OSHA Inspection: ZAP ELECTRICAL CONTRACTORS

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of ZAP ELECTRICAL CONTRACTORS in 930 NORTH RIVERVIEW DRIVE, TOTOWA, NJ 07512 (NAICS 238210). OSHA activity number 308619733.

Watch ZAP Electrical Contractors — free Get an email when a new federal OSHA severe-injury report for ZAP Electrical Contractors is published. One employer, no account, unsubscribe in one click.
Site address
930 NORTH RIVERVIEW DRIVE
City
TOTOWA
State
NJ
ZIP
07512
Mailing
80 THOMAS STREET, PATERSON, NJ 07503
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
SIC code (legacy)
1731
Employees
3
Ownership type
A

1 citation on file for this inspection.

1926.416 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $1500.00
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to employee
in that employee was
exposed to the hazard of arc flash and arc blast:
a) 930 N. Riverview Dr., Totowa/Weston Bakeries' circuit panel: An
employee was exposed
to an arc flash while installing a circuit breaker on a bus energized to
480 Volts.  The employer
proceeded with work on live parts which was not placed in electrically
safe working conditions,
without performing a Flash Hazard Analysis and without using safety
related work practices
based on the determined hazard such as the use of PPE appropriate for
protection from an arc
flash, on or about 03/16/06.
Note: Among other methods, feasible and acceptable abatement methods to
correct this hazard
are:
1. Perform Flash Hazard Analysis to determine the safe working distance
from the panel.
2. Use appropriate tools rated for hazards associated with working on
energized circuits.
3. Use the appropriate PPE for protection against flash hazards such as,
but not
limited to, fire retardant gloves and coveralls.

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 308619733.