Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: DELULLO TRUCKING CORP.

Accident-driven inspection · Health discipline

On , OSHA opened an accident-driven health inspection of DELULLO TRUCKING CORP. in 1022 DELAUM ROAD, ST MARYS, PA 15857 (NAICS 488490). OSHA activity number 309341071.

Watch Delullo Trucking Corp. — free Get an email when a new federal OSHA severe-injury report for Delullo Trucking Corp. is published. One employer, no account, unsubscribe in one click.
Site address
1022 DELAUM ROAD
City
ST MARYS
State
PA
ZIP
15857
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488490
SIC code (legacy)
4231
Employees
22
Ownership type
A

4 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $800.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970 - The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to hazards created by the improper installation of natural
gas-fired equipment:
a.) DeLullo Trucking Corp. Garage Ceiling - the Re-Verber-Ray overhead
infrared
natural gas-fired tube heater was not supplied fresh air from outside the
building.  The
hazard could potentially result in fires and/or the accumulation of
harmful levels of
Carbon Monoxide.
b.) DeLullo Trucking Corp. Garage, northeast corner - the Hydrotek US HN
Series
Natural Gas Powered Pressure Washer was equipped with a manual damper. The
hazard
could potentially result in fires and/or the accumulation of harmful
levels of Carbon
Monoxide.
ABATEMENT NOTE:
Among other methods, feasible and acceptable means to correct the
condition include complying
with the applicable requirements of the National Fuel Gas Code which
states:
NFGC 54/10.8.5 states "All air to the non-recirculating direct gas-fired
industrial heater shall
be ducted directly from outdoors."
NFGC 54/10.18.2 states "Listed heaters shall be installed in accordance
with the manufacturer's
installation instructions."
NFGC 54/12.14 states "A manually operated damper shall not be installed in
any appliance vent
connector."
Page 6 of the manufacturer's (Boyd Lofgren & Co. Re-Verber-Ray, Detroit
Radiant Products
Company) Installation Guide clearly shows the need for outside air to be
supplied to the
appliance.on
Recent events (2)
  • — I (S) $800.00
  • — Z (S) $1500.00

1910.1200 E01

Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $800.00 Reduced
Recent events (2)
  • — I (S) $800.00
  • — Z (S) $1500.00

1910.1200 G01

Deleted Serious Gravity 10 1 instance 22 exposed
Issued
Abate by
Recent events (2)
  • — I (S)
  • — Z (S)

1910.1200 H

Serious Gravity 10 1 instance 22 exposed
Issued
Abate by