Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: WESTERN MASSACHUSETTS ELECTRIC COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of WESTERN MASSACHUSETTS ELECTRIC COMPANY in 53 TERRENCE STREET, SPRINGFIELD, MA 01103 (NAICS 221121). OSHA activity number 310626197.

Watch Western Massachusetts Electric Company — free Get an email when a new federal OSHA severe-injury report for Western Massachusetts Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
53 TERRENCE STREET
City
SPRINGFIELD
State
MA
ZIP
01103
Mailing
30 CADWELL DRIVE, EAST SPRINGFIELD, MA 01104
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
SIC code (legacy)
4911
Employees
190
Ownership type
A

1 citation on file for this inspection.

1910.269 E04

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $6300.00 · Current $3800.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm in that
employees are exposed
to explosion hazards when they remove un-vented manhole covers that have
the potential to
contain explosive atmospheres and potential ignition sources.  Feasible
and acceptable methods
of abatement include, but are not limited to, ensuring that procedures are
developed and
implemented for the removal of the manhole covers when atmospheric
readings are not
obtainable.  Additionally, ensure that all employees receive adequate
training on these
procedures to assure they understand and can demonstrate how to safely
remove these manhole
covers in the event such testing is not feasible.
A) LOCATION: 43 TERRENCE ST, SPRINGFIELD MA
ON 11/16/07, TWO WORKERS INVOLVED IN THE REMOVAL OF A MANHOLE COVER
WHERE EXPOSED TO A NATURAL GAS EXPLOSION WHEN THEY REMOVED A
MANHOLE COVER PRIOR TO CONFIRMING A SAFE ATMOSPHERE EXISTED IN THE
SPACE.  THE MANHOLE CONTAINED AN EXPLOSIVE CONCENTRATION OF
NATURAL GAS CREATED BY AN UNDERGROUND GAS LEAK AND WHEN THE
COVER WAS SLID BACK AN EXPLOSION OCCURRED WHICH RESULTED IN SEVERE
BURNS TO AN EMPLOYEE'S FACE. THE CURRENT PROCEDURES DO NOT INCLUDE
STEPS TO TAKE WHEN ATMOSPHERIC MONITORING PRIOR TO ENTRY IS NOT
FEASIBLE.
Recent events (2)
  • — I (S) $3800.00
  • — Z (S) $6300.00

View WESTERN MASSACHUSETTS ELECTRIC COMPANY's full OSHA safety record →

PSE&G