OSHA Inspection: WESTERN MASSACHUSETTS ELECTRIC COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WESTERN MASSACHUSETTS ELECTRIC COMPANY in REAR OF 10 CONTE DR. FEDERAL RECORDS CENTER, PITTSFIELD, MA 01201 (NAICS 221122). OSHA activity number 313209793.

Watch Western Massachusetts Electric Company — free Get an email when a new federal OSHA severe-injury report for Western Massachusetts Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
REAR OF 10 CONTE DR. FEDERAL RECORDS CENTER
City
PITTSFIELD
State
MA
ZIP
01201
Mailing
333 WEST STREET, PITTSFIELD, MA 01201
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
SIC code (legacy)
4911
Employees
350
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 05 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $6000.00
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized
hazards that
were causing or likely to cause death or serious physical harm in that
employees were exposed
to falls of approximately 20 feet when a fiberglass extension ladder,
Werner Model 7124-2, was
used to climb a power pole in the right of way behind 10 Conte Drive,
Pittsfield, Massachusetts
on April 15, 2011. The ladder used on the power pole had a standard top
rung and no v-rung
which is designed to prevent sliding of the ladder during climbing
operations. The employee
climbed the extension ladder while wearing pole climbing gaffs which do
not provide a non-slip
surface while on the ladder and the employee climbed from the top rung of
the ladder onto the
pole. Among other methods, one feasible and acceptable abatement methods
to correct this
harzard would be to have the employee climb the pole using gaffs and a
climbing belt.  Another
acceptable method to correct this hazard would be to have the employee
work from an insulated
bucket elevated from a truck.
Recent events (2)
  • — I (S)
  • — Z (S) $6000.00

1910.269 A02 III

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
Recent events (3)
  • — F (S) $7000.00
  • — I (S) $7000.00
  • — Z (S) $7000.00

1904.29 B01

Deleted Other-than-serious Gravity 00 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1000.00
Recent events (2)
  • — I (O)
  • — Z (O) $1000.00

1904.29 B01

Deleted Other-than-serious Gravity 00 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $1000.00
Recent events (2)
  • — I (O)
  • — Z (O) $1000.00

1904.29 B01

Deleted Other-than-serious Gravity 00 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $1000.00
Recent events (2)
  • — I (O)
  • — Z (O) $1000.00