CONNEAUT, OH —
OSHA Inspection: PLYCRAFT
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of PLYCRAFT in 557 W. MAIN ST., CONNEAUT, OH 44030 (NAICS 321999). OSHA activity number 311505002.
Where did this inspection happen?
- Establishment
- PLYCRAFT
- Site address
- 557 W. MAIN ST.
- City
- CONNEAUT
- State
- OH
- ZIP
- 44030
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321999
- SIC code (legacy)
- 2499
- Employees
- 31
- Ownership type
- A
Citations
7 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $875.00 · Current $875.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to severe burns from the potential dust explosion, deflagration and fire hazards caused by the improper design, and maintenance of dust collection system. a.A section of duct located over the ship lap machine was covered with combustible duct tape material. b.A duct end in use was covered with a wood cap held in place with combustible duct tape. c.The ducts did not have deflagration venting, fire protection or explosion suppression systems. d.The fans and blowers were located on the dirty side of the dust collecting system. e.The dust collection systems in both the old and new buildings were never balanced. f.None of the ducts were grounded. g.None of the dust collectors had deflagration venting. ABATEMENT NOTE-Among other methods, one feasible and acceptable abatement method to correct these hazards is to have a qualified engineer inspect the dust collection system to ensure that it is designed and installed in accordance with National Fire Protection Association (NFPA) 664-2007, Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities. Abatement measures include: *Repair the gap in the section of duct with non-combustible material; *Design, construct, and install ducts with metal sufficient to withstand the maximum unvented deflagration pressure, explosion suppression systems, or deflagration relief venting; *Relocate the fan to the clean side of the dust collector; *Balance and re-balance, as necessary, the dust collection system; *Bond and ground the dust collection system ductwork with such methods as listed in NFPA 664-2007, paragraph 7.6.2; *Install deflagration isolation or suppression systems, or deflagration relief venting on the dust collectors.
Recent events (3)
- — P (S) $875.00
- — F (S) $875.00
- — Z (S) $875.00
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $875.00
Recent events (2)
- — F (S)
- — Z (S) $875.00
1910.23 C03
- Issued
- Abate by
- Penalty
- Initial $700.00 · Current $490.00 Reduced
Recent events (2)
- — F (S) $490.00
- — Z (S) $700.00
1910.134 C02 I
- Issued
- Abate by
- Penalty
- Initial $525.00
Recent events (2)
- — F (O)
- — Z (S) $525.00
1910.134 C02 II
- Issued
- Abate by
Recent events (2)
- — F (O)
- — Z (S)
1910.147 C04 IB
- Issued
- Abate by
- Penalty
- Initial $875.00 · Current $613.00 Reduced
Recent events (2)
- — F (S) $612.50
- — Z (S) $875.00
1910.219 F03
- Issued
- Abate by
- Penalty
- Initial $525.00 · Current $368.00 Reduced
Recent events (2)
- — F (S) $367.50
- — Z (S) $525.00
More inspections in this industry (NAICS 321999)
LAURINBURG, NC—2026-07-14 00:00:00
161549 - AMERICAN WOOD FIBERS, INC.
NEWINGTON, CT—2026-07-14 00:00:00
TRUSS MANUFACTURING INC
NORTH WILKESBORO, NC—2026-07-07 00:00:00
161501 - MILLER BEE SUPPLY, INC.
MIAMI, FL—2026-06-26 00:00:00
FLORIDA LUMBER COMPANY
PLATO, MN—2026-06-25 00:00:00
111471 - STEVE TUSHA DBA GREAT OAK EQUINE
More inspections in OH
DAYTON, OH—2026-07-17 00:00:00
TEKNOL, INC.
PAYNE, OH—2026-07-16 00:00:00
LIPPERT
SUGARCREEK, OH—2026-07-16 00:00:00
PROVIA
CINCINNATI, OH—2026-07-16 00:00:00
GREENACRES FOUNDATION
WELLINGTON, OH—2026-07-16 00:00:00
WHIRLAWAY CORPORATION
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 311505002.