Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: PEACOCK OIL COMPANY

Accident-driven inspection · Health discipline

On , OSHA opened an accident-driven health inspection of PEACOCK OIL COMPANY in 1060 E. PARK AVENUE, LIBERTYVILLE, IL 60048 (NAICS 447110). OSHA activity number 311718928.

Watch Peacock OIL Company — free Get an email when a new federal OSHA severe-injury report for Peacock OIL Company is published. One employer, no account, unsubscribe in one click.
Establishment
PEACOCK OIL COMPANY
Site address
1060 E. PARK AVENUE
City
LIBERTYVILLE
State
IL
ZIP
60048
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
447110
SIC code (legacy)
5541
Employees
8
Ownership type
A

4 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $3500.00

Hazardous substances 0560

Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to accumulated fuel gases and potential fire, and oxygen
deficient atmospheres.
a) Peacock Oil Company, South Equipment Room - Gas utilization equipment
including: Raypak
Heating Boiler, Model 724 WT-B, Serial Number 0988106022;  Raypak Heating
Boiler, Model
516T, Serial Number 1278103800TP; and, Dayton Unit Heater, Model 3E226A,
Serial Number
C8412734, installed in buildings: Required air was not supplied for
combustion and ventilation,
nor for comfort and proper working conditions for personnel.
One feasible means of abatement, among others is to provide the space with
two permanent
openings to the outdoors, one commencing within 12 inches of the top and
one commencing
within 12 inches of the bottom of the enclosure and which conforms to NFPA
54 - National Fuel
Gas Code. NFPA 54 (1988) states that the "openings shall communicate
directly or by ducts,
with the outdoors or spaces (crawl or attic) that freely communicate with
the outdoors.  When
directly communicating with the outdoors, for example, each opening shall
have a minimum free
area of 1 square inch per 4000 BTU per hour of total input rating of all
equipment in the
enclosure." (Chapter 5.3.3)
In accordance with 29 CFR 1903.19(d), abatement certification is required
for this violation
(using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in
addition, documentation demonstrating that abatement is complete must be
included with
your certification.  This documentation may include, but is not limited
to, evidence of the
purchase or repair of the equipment, photographic or video evidence of
abatement, or other
written records.
Recent events (2)
  • — I (S) $3500.00
  • — Z (S) $3500.00

1910.151 C

Serious Gravity 03 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1250.00 · Current $1250.00

Hazardous substances 22601460

Recent events (2)
  • — I (S) $1250.00
  • — Z (S) $1250.00

1910.1000 A02

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $7000.00

Hazardous substances C730

Recent events (2)
  • — I (S) $7000.00
  • — Z (S) $3500.00

1910.1000 E

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by

Hazardous substances C730

Recent events (2)
  • — I (S)
  • — Z (S)

AK, INC

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 311718928.