OSHA Inspection: PRAIRIE FIRE BIOENERGY COOPERATIVE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PRAIRIE FIRE BIOENERGY COOPERATIVE in 97 W. HIGHWAY 4, HEALY, KS 67850 (NAICS 325199). OSHA activity number 312796873.

Watch Prairie Fire Bioenergy Cooperative — free Get an email when a new federal OSHA severe-injury report for Prairie Fire Bioenergy Cooperative is published. One employer, no account, unsubscribe in one click.
Site address
97 W. HIGHWAY 4
City
HEALY
State
KS
ZIP
67850
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325199
SIC code (legacy)
2899
Employees
13
Ownership type
A

6 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $750.00 Reduced
Section 5(a)1 of the Occupational Safety and Health Act of 1970: The
employer did not furnish
employment and a place of employment which were free from recognized
hazards that were
causing or likely to cause death or serious physical harm to employees in
that employees were
exposed to fire and explosion hazards:
Employees working in the pelletizing plant were exposed to fire and
explosion hazards
for the following instances:
a)Employees were exposed to fire and explosion hazards created by
combustible dusts generated in the process of making fuel pellets in that
a dust collection system was not used.
Among other methods, one feasible and acceptable method to correct this
hazard
is to install a dust collection system as referenced in NFPA 654,
Prevention of
Fire and Dust Explosions of Combustible Particulate Solids, 2006 Edition,
paragraph 8.1.1 Fugitive Dust Control "Continuous suction to minimize the
escape of dust shall be provided for processes where combustible dust is
liberated
in normal operation."
b)Employees were exposed to fire and explosion hazards created by exhaust
fan installed on the west wall to pull dust out of the building.
Among other methods, one feasible and acceptable method to correct this
hazard
is to not use the exhaust fan a means of dust control.  NFPA 654,
Prevention of
Fire and Dust Explosions of Combustible Particulate Solids, 2006 Edition,
paragraph 7.12.2.1 Combustible Particulate Solids, states "Where an
explosion
hazard exists, systems shall be designed in such a manner that combustible
particulate solids do not pass through an air-moving device."
29 CFR 1903.19(d)(1) requires certification and documentation that the
abatement of the
above violation is completed.
Recent events (2)
  • — I (S) $750.00
  • — Z (S) $1500.00

1910.22 A01

Serious Gravity 03 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $750.00 · Current $375.00 Reduced
Recent events (2)
  • — I (S) $375.00
  • — Z (S) $750.00

1910.134 C01

Serious Gravity 01 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $450.00 · Current $225.00 Reduced
Recent events (2)
  • — I (S) $225.00
  • — Z (S) $450.00

1910.134 E01

Serious Gravity 01 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $450.00 · Current $225.00 Reduced
Recent events (2)
  • — I (S) $225.00
  • — Z (S) $450.00

1910.134 K01

Serious Gravity 01 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $450.00 · Current $225.00 Reduced
Recent events (2)
  • — I (S) $225.00
  • — Z (S) $450.00

1910.307 C02 I

Serious Gravity 03 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $750.00 · Current $375.00 Reduced
Recent events (3)
  • — P (S) $375.00
  • — I (S) $375.00
  • — Z (S) $750.00