Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LOUIE KNAPP JR. DBA KNAPP HOMES & IMPROVEMENTS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of LOUIE KNAPP JR. DBA KNAPP HOMES & IMPROVEMENTS in 820 CENTER STREET, FORREST, IL 61741 (NAICS 337122). OSHA activity number 312885189.

Watch Louie Knapp JR. DBA Knapp Homes & Improvements — free Get an email when a new federal OSHA severe-injury report for Louie Knapp JR. DBA Knapp Homes & Improvements is published. One employer, no account, unsubscribe in one click.
Site address
820 CENTER STREET
City
FORREST
State
IL
ZIP
61741
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337122
SIC code (legacy)
2511
Employees
3
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $900.00 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that:
Employees in the Shop Area were exposed to fire and explosion hazards
while performing
routine work near the Hammond Duskolector (Model DK-8), which did not have
adequate
explosion prevention or suppression systems for the handling of
combustible wood dust.
NFPA Standard 664 - 2007 Standard for the Prevention of Fires and
Explosions in Wood
Processing and Woodworking Facilities:
Section 8.2.2.5.1.4: "Dust collectors shall be located in accordance with
one of the
following: outside of buildings, indoors when deemed to have no fire or
deflagration hazard,
indoors for dust collectors with only a fire hazard when protected in
accordance
with this
standard, indoors when equipped with listed deflagration suppression
system, indoors when
equipped with deflagration relief vents with relief pipes extending to
safe areas outside the
building and the collector meets the strength requirement of this
standard, indoors when
equipped with deflagration relief vents exhausting through listed
flame-quenching devices and
the collector meets the strength requirement of this standard.
Among other methods, feasible and acceptable abatement method(s) to
correct this hazard is
to comply with the guidelines of NFPA 664 - 2007 Standard for the
Prevention of Fires and
Explosions in Processing and Woodworking Facilities:
a) Relocate the dust collection unit to the exterior of the building; or
b) Equip system with a listed deflagration suppression system; or
c) Equip system with deflagration relief pipes extending to safe areas
outside the
building and the collector meets the strength requirement of NFPA 664; or
d) Equip system with deflagration relief vents exhausting through listed
flame-
quenching devices and the collector meets the strenth requirement of 664;
or
e) Switch to an enclosureless dust collection unit that meets the
requirement of NFPA
664.
***Abatement documentation is required for this item in accordance with the
requirements of 29 CFR 1903.19(d)***
Recent events (2)
  • — I (S) $900.00
  • — Z (S) $1500.00

1910.22 A02

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $900.00 Reduced
Recent events (2)
  • — I (S) $900.00
  • — Z (S) $1500.00

1910.95 C01

Serious Gravity 10 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $1500.00 · Current $900.00 Reduced
Recent events (2)
  • — I (S) $900.00
  • — Z (S) $1500.00

View LOUIE KNAPP JR. DBA KNAPP HOMES & IMPROVEMENTS's full OSHA safety record →