TUPELO, MS —
OSHA Inspection: JESCO MAINTENANCE CORPORATION
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of JESCO MAINTENANCE CORPORATION in 1804 S. GREEN ST., TUPELO, MS 38804 (NAICS 811310). OSHA activity number 313635005.
Where did this inspection happen?
- Establishment
- JESCO MAINTENANCE CORPORATION
- Site address
- 1804 S. GREEN ST.
- City
- TUPELO
- State
- MS
- ZIP
- 38804
- Mailing
- 2020 MCCULLOUGH BLVD, TUPELO, MS 38802
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- SIC code (legacy)
- 7699
- Employees
- 213
- Ownership type
- A
Citations
12 citations on file for this inspection.
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to Class II combustible dust explosion hazards due to the carbon black dust handling systems were not equipped with safety devices as to: On or about December 7-8, 2010 on the roof and 2nd floor of the mixing department, employees were exposed to combustible dust fire and explosion hazards due to the employer's failure to protect the carbon black dust storage silos, conveying systems, day bins, cyclones, and dust collectors with an adequate venting, suppression system, or suppression system. (a)The pneumatic/vacuum duct system used to transfer carbon black from the tank railcars and tank trailers was not provided with a fire detection and isolation system. (b)The eight (8) main storage silos located outside and away from the building were not provided with deflagration/explosion protection systems. (c)The eight (8) inch diameter pneumatic/vacuum conveying duct that transfers carbon black from the silos to the day bins on the roof of the building above the banbury mixers was not provided with a fire detection system and isolation system. (d)The particle size separators (cyclones) on top of the two day bins ("E" Day Bin for banbury mixer #4 and "D" Day Bin for banbury mixer #3) were not provided with deflagration/explosion protection, fire detection, and suppression systems. (e)The air material separators (dust collectors) on top of the two day bins ("E" Day Bin for banbury mixer #4 and "D" Day Bin for banbury mixer #3) were not provided with deflagration/explosion systems, fire detection, and suppression systems. (f)The two day bins, "E" Day Bin for banbury mixer #4 and "D" Day Bin for banbury mixer 3 were four (4) compartment silos located on top of the roof above the master batch mixers. They were not provided with deflagration/explosion protection systems. (g)The duct work system drawing carbon black dust from the charging areas for banbury mixers 3 and 4 were not provided with a fire detection and isolation systems. (h)The enclosed screw conveyor systems for mixers 3 and 4 used to return the carbon black dust, drawn from the charging areas, back to the scales for recycling were not provided with a fire detection and isolation systems. Among others, one feasible and useful abatement method to correct these hazards is to follow the requirements found in NFPA 69, 91, and 654.
Recent events (2)
- — F (S) $7000.00
- — Z (S) $7000.00
5(a)(1)
- Issued
- Abate by
- Penalty
- Initial $4000.00 · Current $2500.00 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck by hazards due to defective safety latches and un-labeled below-the-hook lifting device as to; (a)On or about December 7, 2010 on the first floor, the hoist used to lower drums of sledge waste from the mezzanine had a defective safety latch. (b)On or about December 7, 2010 on the first floor, the below-the-hook lifting device used to lower drums of sledge from the mezzanine was not labeled with the manufacturer's name, serial number, and load capacity. Among others, one feasible and useful abatement method to correct these hazards is to follow the requirements in ASME B30.10-2009 "Hooks". Among others, one feasible and useful abatement method to correct these hazards is to follow the requirements in ASMS B30.20-2006 "Below-the-Hook Lifting Devices".
Recent events (2)
- — F (S) $2500.00
- — Z (S) $4000.00
1910.22 A01
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $2500.00 Reduced
Recent events (2)
- — F (S) $2500.00
- — Z (S) $7000.00
1910.22 A02
- Issued
- Abate by
Recent events (2)
- — F (S)
- — Z (S)
1910.23 C03
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $3000.00 Reduced
Recent events (2)
- — F (S) $3000.00
- — Z (S) $7000.00
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $5000.00 · Current $3000.00 Reduced
Recent events (2)
- — F (S) $3000.00
- — Z (S) $5000.00
1910.303 G01
- Issued
- Abate by
- Penalty
- Initial $3000.00 · Current $3000.00
Recent events (2)
- — F (S) $3000.00
- — Z (S) $3000.00
1910.305 G01 IVA
- Issued
- Abate by
- Penalty
- Initial $4000.00 · Current $2500.00 Reduced
Recent events (2)
- — F (S) $2500.00
- — Z (S) $4000.00
1910.305 G02 II
- Issued
- Abate by
Recent events (2)
- — F (S)
- — Z (S)
1910.307 C02
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
Recent events (2)
- — F (S) $7000.00
- — Z (S) $7000.00
1910.305 B02
- Issued
- Abate by
Recent events (2)
- — F (O)
- — Z (O)
1910.305 G02 III
- Issued
- Abate by
Recent events (2)
- — F (O)
- — Z (O)
More inspections at JESCO MAINTENANCE CORPORATION
TUPELO, MS—2017-05-11 00:00:00
JESCO MAINTENANCE CORPORATION
TUPELO, MS—2012-10-02 00:00:00
JESCO MAINTENANCE CORPORATION
View JESCO MAINTENANCE CORPORATION's full OSHA safety record →
More inspections in this industry (NAICS 811310)
CHRISTIANSBURG, VA—2026-07-09
BGIS GLOBAL INTEGRATED SOLUTION US, LLC
SEATTLE, WA—2026-07-09
WA317992010 - FLAGSHIP MANAGEMENT LLC
STATESBORO, GA—2026-07-08
TAYLOR BUILT PRODUCTS
, AK—2026-07-08
ANGUS ENTERPRISES
LOS ANGELES, CA—2026-07-08
CHILLEST INDUSTRIES LLC
More inspections in MS
LAUREL, MS—2026-07-01
THERMO-KOOL
HORN LAKE, MS—2026-07-01
NEWLY WEDS FOODS, INC.
GAUTIER, MS—2026-07-01
DOUBLE R GAUTIER, LLC
OLIVE BRANCH, MS—2026-06-30
HYVE SOLUTIONS
GAUTIER, MS—2026-06-30
STEVE WILSON ENTERPRISE
Source