COLUMBUS, OH —
OSHA Inspection: OHIO VALLEY CABLE SERVICES
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of OHIO VALLEY CABLE SERVICES in 1030 FREEWAY DRIVE, COLUMBUS, OH 43229 (NAICS 517510). OSHA activity number 330986480.
Where did this inspection happen?
- Establishment
- OHIO VALLEY CABLE SERVICES
- Site address
- 1030 FREEWAY DRIVE
- City
- COLUMBUS
- State
- OH
- ZIP
- 43229
- Mailing
- 1030 FREEWAY DRIVE, COLUMBUS, OH 43229
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 517510
- Employees
- 235
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.138 A
- Issued
- Abate by
- Penalty
- Initial $2295.00 · Current $1607.00 Reduced
General-duty citation text
29 CFR 1910.138(a): General requirements. Employers shall select and require employees to use appropriate hand protectionwhen employees' hands are exposed to hazards such as those from skin absorption of harmful substances; severe cuts or lacerations; severe abrasions;punctures; chemical burns; thermal burns; and harmful temperature extremes. a. In the warehouse, forklift operators who were exposed to sulfuric acid while performing battery maintenance were provided with latex gloves.
Recent events (2)
- — I (S) $1606.5
- — Z (S) $2295
1910.305 A01 I
- Issued
- Abate by
- Penalty
- Initial $2295.00 · Current $1607.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(1)(i): Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and other metal noncurrent-carrying parts that are to serve as grounding conductors, with or without the use of supplementary equipment grounding conductors, shall be effectively bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them. Any nonconductive paint, enamel, or similar coating shall be removed at threads, contact points, and contact surfaces or be connected by means of fittings designed so as to make such removal unnecessary. a. In the warhouse, the metal conduit surrounding the flexible electrical cable on the Kodiak charger was not adequately bonded to its fitting.
Recent events (2)
- — I (S) $1606.5
- — Z (S) $2295
More inspections in this industry (NAICS 517510)
WICKLIFFE, KY—2024-11-04 00:00:00
67511 - TREASURE LAKE LP
CAMANO ISLAND, WA—2022-12-29 00:00:00
WA317971953 - WAVEDIVISION I LLC
RANDLE, WA—2021-08-09 00:00:00
WA317965207 - WAVEDIVISION VI, LLC
SEATTLE, WA—2021-05-24 00:00:00
WA317964204 - WAVEDIVISION I LLC
NACHES, WA—2021-04-20 00:00:00
WA317963665 - ECHOSTAR SATELLITE LLC
More inspections in OH
WELLINGTON, OH—2026-07-16 00:00:00
WHIRLAWAY CORPORATION
WAUSEON, OH—2026-07-16 00:00:00
WATSON WELL DRILLING INC.
SEVEN HILLS, OH—2026-07-15 00:00:00
STONEY ACRES BUILDERS LLC
SEVEN HILLS, OH—2026-07-15 00:00:00
GRB ENTERPRISES LLC
CHILLICOTHE, OH—2026-07-15 00:00:00
KENWORTH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330986480.