Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: CHERYL & CO.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CHERYL & CO. in 646 MCCORKLE BLVD, WESTERVILLE, OH 43082 (NAICS 311821). OSHA activity number 331086462.

Watch Cheryl & CO. — free Get an email when a new federal OSHA severe-injury report for Cheryl & CO. is published. One employer, no account, unsubscribe in one click.
Establishment
CHERYL & CO.
Site address
646 MCCORKLE BLVD
City
WESTERVILLE
State
OH
ZIP
43082
Mailing
646 MCCORKLE BLVD, WESTERVILLE, OH 43082
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311821
Employees
250
Ownership type
A

2 citations on file for this inspection.

1910.303 G01 II

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4250.00 · Current $4250.00
29 CFR 1910.303(g)(1)(ii):     The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    a) On, 11/03/2011, at the workplace, in the Kitchen Area, an electrical supply box, had insufficient clearance between the front of the enclosure and the baking materials stored in front of it.
Recent events (1)
  • — Z (S) $4250

1910.304 G05

Serious Gravity 5 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $3400.00 · Current $3400.00
29 CFR 1910.304(g)(5):     Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.    a) On 11/03/11 at the workplace, in the Cooling Area, a 30" Commercial Duty Circulator, manufactured by Dayton, was ungrounded causing the unit's casing to become electrically live. The grounding pin had been bent and broken loose inside the plug's housing preventing a continuous path.        b) On 11/03/11 at the workplace, in the Packing Area, a 30" Commercial Duty Circulator, manufactured by Dayton, was ungrounded causing the unit's casing to become electrically live. The grounding pin had been broken off or removed from the plug's housing preventing a continuous path.
Recent events (1)
  • — Z (S) $3400