NEW RICHMOND, WI —
OSHA Inspection: WISCONSIN WIRE CLOTH
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WISCONSIN WIRE CLOTH in 400 WISCONSIN DRIVE, NEW RICHMOND, WI 54017 (NAICS 332618). OSHA activity number 332798172.
Where did this inspection happen?
- Establishment
- WISCONSIN WIRE CLOTH
- Site address
- 400 WISCONSIN DRIVE
- City
- NEW RICHMOND
- State
- WI
- ZIP
- 54017
- Mailing
- 400 WISCONSIN DRIVE, NEW RICHMOND, WI 54017
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332618
- Employees
- 13
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.212 A03 II
- Issued
- Abate by
- Penalty
- Initial $4200.00 · Current $2520.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): (a) Throughout the facility; Employees were exposed to point of operations hazard on production machinery such as, but not limited to; (1) Main production area; wire looms; The point of operation created by the slammer and cross wires or the frame of the machinery, and (2)West end of warehouse; The point of operation on the HTC Press Brake.
Recent events (3)
- — F (S) $2520
- — C (S) $4200
- — Z (S) $4200
1910.303 B07 I
- Issued
- Abate by
- Penalty
- Initial $3600.00 · Current $2160.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a) West end of warehouse area, HTC Press Brake: The power switch box for the press brake was damaged exposing the conductors inside.
Recent events (2)
- — I (S) $2160
- — Z (S) $3600
1910.305 G01 IV A
- Issued
- Abate by
- Penalty
- Initial $2400.00 · Current $1440.00 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) West end of warehouse area, vicinity of the HTC Press Brake: A flexible yellow extension cord being used to energize power tools at a work station was tied around part of the building structure and strung through the frame of a press brake.
Recent events (2)
- — I (S) $1440
- — Z (S) $2400
1910.305 G01 IV D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: (a) West end of warehouse area, vicinity of the HTC Press Brake: A flexible yellow extension cord was tied around the buildings structure.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) West end of warehouse, vicinity of the HTC Press Brake: A flexible yellow extension cord powering hand tools at an employee work station exhibited strain relief where it was plugged into the wall outlet.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.178 L04 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years: (a) Throughout the facility; An evaluation of each power industrial vehicle operator was not conducted within three years.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 332618)
HOUSTON, TX—2026-07-17 00:00:00
HOLLOWAY HOUSTON, INC.
WINONA, MN—2026-07-16 00:00:00
111609 - HIATT METAL FORMING LLC
ADDISON, IL—2026-07-15 00:00:00
BETTER BILT PRODUCTS INC.
MANSFIELD, MA—2026-07-15 00:00:00
REXEL USA, INC.
WINONA, MN—2026-07-14 00:00:00
111592 - PEERLESS CHAIN COMPANY
More inspections in WI
GREEN BAY, WI—2026-07-17 00:00:00
PTS CONTRACTORS, INC.
WAUSAU, WI—2026-07-16 00:00:00
MIRON CONSTRUCTION CO. INC.
ELROY, WI—2026-07-15 00:00:00
WABASH NATIONAL SERVICES, L.P.
SUSSEX, WI—2026-07-15 00:00:00
KINGS SUPERIOR CONSTRUCTION LLC
DELAVAN, WI—2026-07-15 00:00:00
TERONOMY BUILDERS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 332798172.