Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: DOLCO PACKAGING A TEKNI-PLEX COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DOLCO PACKAGING A TEKNI-PLEX COMPANY in 210 INDUSTRIAL PARKWAY, SOMERVILLE, NJ 08876 (NAICS 326199). OSHA activity number 334134624.

Watch Dolco Packaging A Tekni-Plex Company — free Get an email when a new federal OSHA severe-injury report for Dolco Packaging A Tekni-Plex Company is published. One employer, no account, unsubscribe in one click.
Site address
210 INDUSTRIAL PARKWAY
City
SOMERVILLE
State
NJ
ZIP
08876
Mailing
201 INDUSTRIAL PARKWAY, SOMERVILLE, NJ 08876
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
130
Ownership type
A

2 citations on file for this inspection.

1910.119 J04 I

Serious Gravity 5 1 instance 11 exposed
Issued
Penalty
Initial $3740.00 · Current $2431.00 Reduced
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment to maitain its mechanical integrity:    Tekni-Plex Branchburg NJ site - Formacel Z-2 bulk storage tank (s/n: 119251):     a) The employer did not perform inspections and testing on the underground piping (1-HFC-4-P) from the Z-2 tank to the high pressure pump room.    b) The employer did not perform inspections and non-destructive testing on above ground piping lines leading to the storage tank from the delivery truck and from the storage tank to the underground tranfer lines.    Condition noted on or about 6/1/2012.
Recent events (2)
  • — I (S) $2431
  • — Z (S) $3740

1910.119 J04 II

Serious Gravity 5 1 instance 11 exposed
Issued
Penalty
Initial $3740.00 · Current $2431.00 Reduced
29 CFR 1910.119(j)(4)(ii): Inspections and testing procedures performed on process equipment to maintain its mechanical integrity did not follow recognized and generally accepted good engineering practices (RAGAGEP):    a) Tekni-Plex Branchburg NJ site - Formacel Z-2 bulk storage tank (s/n: 119251):    The employer did not comply with RAGAGEP such as but not limited to API 510 section 6.5.1 when it failed to internally inspect the 152a difluoroethane storage tank a minimum of one half the remaining life of the vessel or every 10 years.    Condition noted on or about 6/1/2012.
Recent events (2)
  • — I (S) $2431
  • — Z (S) $3740

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334134624.