ARANSAS PASS, TX —
OSHA Inspection: PINNACLE HEALTH FACILITIES OF TEXAS X.V., L.P.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of PINNACLE HEALTH FACILITIES OF TEXAS X.V., L.P. in 1661 W. YOAKUM, ARANSAS PASS, TX 78336 (NAICS 623110). OSHA activity number 334342169.
Where did this inspection happen?
- Establishment
- PINNACLE HEALTH FACILITIES OF TEXAS X.V., L.P.
- Site address
- 1661 W. YOAKUM
- City
- ARANSAS PASS
- State
- TX
- ZIP
- 78336
- Mailing
- 1661 W YOAKUM AVE, ARANSAS PASS, TX 78336
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623110
- Employees
- 115
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.219 F03
- Issued
- Abate by
- Penalty
- Initial $3060.00 · Current $1836.00 Reduced
General-duty citation text
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven -7 feet or less above floors or platforms were not enclosed: In the Laundry building on Dryer #1, employees clean walking/working surfaces behind dryers and make machinery repairs were exposed to being caught-in the unguarded chain and sprocket on the motor which was adjacent to the doorway, approximately three feet above ground level.
Recent events (2)
- — I (S) $1836
- — Z (S) $3060
1910.303 E01 II
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $2295.00 Reduced
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electric equipment shall not be used unless markings have been placed on equipment such as voltage, current, wattage and other ratings as necessary: At this facility, energized electric panels did not have any identifying markings, employees who inspect, operate and/or touch electrical components are exposed to shock or death by electrocution such as but not limited to the following: a. In the Laundry Building on the east wall behind the washers, the electric panel has six circuit breakers and there are no markings indicating the amperage, voltage, manufactures name etc. b. In the Maintenance Building on the west wall, there are two electric panels with several circuit breakers without identifying markings for voltage, amperage, etc.
Recent events (2)
- — I (S) $2295
- — Z (S) $3825
1910.303 F02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: At this facility, employees inspect, operate and/or touch electrical components in panels are exposed to shock or death by electrocution such as but not limited to the following: a. In the Laundry Building on the east wall behind the washers, the electric panel had six circuit breakers and five were unidentified as to their purpose or function. b. In the Maintenance Building on the west wall, a smaller electric panel with eight unidentified circuit breakers. c. In the Maintenance Building on the west wall, a large electric panel with four unidentified circuit breakers.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $2295.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: In the Maintenance Building at this facility, where employees make repairs, sharpen tools, and store furniture; access to the two electric panels on the west wall were blocked by a mattress, a bed frame, and boxes of various goods.
Recent events (2)
- — I (S) $2295
- — Z (S) $3825
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: In the Maintenance Building on the west wall, the small electric panel on the left with eight circuit breakers had a large unused opening on the left side of the box.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $2295.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: In the Maintenance Building, employees work with cord and plug machinery to sharpen tools and the electric panel did not have a faceplate installed to protect employees from contact with energized conductors.
Recent events (2)
- — I (S) $2295
- — Z (S) $3825
1904.29 B01
- Issued
- Penalty
- Initial $765.00 · Current $459.00 Reduced
General-duty citation text
29 CFR 1904.29(b)(1): A Log of all recordable work-related injuries and illnesses (OSHA Form 300 or equivalent), was not completed in detail as required by the regulation: At Lexington Place Nursing & Rehabilitation: On or about May 17, 2012, the employer did not correctly record the following work-related injuries or illnesses on the OSHA Form 300 or equivalent for the calendar year 2012: a. On or about January 2, 2012, CNA - an employee received a sprain to the wrist and hand and the employer did not enter a check mark in columns J or indicate the number of days in column L, when the case resulted in days of job transfer or restriction. b. On or about March 12, 2012, Dietary worker - an employee experienced pain to foot and ankle and the employer did not enter a check mark in columns J or indicate the number of days in column L, when the case resulted in days of job transfer or restriction.
Recent events (2)
- — I (O) $459
- — Z (O) $765
More inspections at PINNACLE HEALTH FACILITIES OF TEXAS X.V., L.P.
ARANSAS PASS, TX—2013-04-16 00:00:00
PINNACLE HEALTH FACILITIES OF TEXAS X.V., L.P.
View PINNACLE HEALTH FACILITIES OF TEXAS X.V., L.P.'s full OSHA safety record →
More inspections in this industry (NAICS 623110)
GRANTS PASS, OR—2026-07-07
317744714 - CASCADE LIVING GROUP - GRANTS PASS LLC
TIFFIN, OH—2026-06-30
670 OH OPCO, LLC
EDMONDS, WA—2026-06-25
WA317991719 - KALESTA HEALTHCARE GROUP LLC
LINCOLNTON, NC—2026-06-24
161444 - LINCOLNTON REHABILITATION CENTER, LLC
CENTRALIA, WA—2026-06-23
WA317991797 - PROVIDENCE HEALTH & SERVICES WASHINGTON
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334342169.