JEFFERSON, GA —
OSHA Inspection: ESCOE INDUSTRIAL CONTRACTORS, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of ESCOE INDUSTRIAL CONTRACTORS, INC. in 2516 VALENTINE INDUSTRIAL PARKWAY, JEFFERSON, GA 30549 (NAICS 238210). OSHA activity number 335002788.
Where did this inspection happen?
- Establishment
- ESCOE INDUSTRIAL CONTRACTORS, INC.
- Site address
- 2516 VALENTINE INDUSTRIAL PARKWAY
- City
- JEFFERSON
- State
- GA
- ZIP
- 30549
- Mailing
- 650 OLYMPIC DR., ATHENS, GA 30601
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.416 A03
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $6300.00
General-duty citation text
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit On or about July 3, 2012: (a) Employees were engaged in the installation of electrical equipment to provide power to space heaters used to regulate condensation within the switchgear cabinet located within a substation, were exposed to electrical shock and arc flash hazards. As employer failed to establish through inquiry, direct observation or testing that electrical equipment was energized.
Recent events (1)
- — Z (S) $6300
1926.957 A02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.957(a)(2)(i): When work was to be done in an energized substation, a determination was not made as to what facilities were energized at the time of the work. On or about July 3, 2012: (a) Employees were engaged in the installation of electrical equipment to provide power to space heaters used to regulate condensation within the switchgear cabinet located within a substation. The employees were exposed to electrical shock and arc flash hazards as the employer failed to ensure that electrical components were properly identified as energized before work on electrical components was performed.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 238210)
PARKVILLE, MD—2026-07-15 00:00:00
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15 00:00:00
EDGE ELECTRICAL SYSTEMS, LLC
LAYTON, UT—2026-07-14 00:00:00
LYNN WOODWARD ELECTRIC LLC
BRIDGEPORT, WV—2026-07-14 00:00:00
INFINITY ELECTRIC & SERVICE COMPANY, LLC
ANNAPOLIS, MD—2026-07-14 00:00:00
J.M. MULLEN ELECTRICAL SERVICES, INC.
More inspections in GA
GREENSBORO, GA—2026-07-16 00:00:00
PURE BEAUTY FARMS, INC.
FOREST PARK, GA—2026-07-16 00:00:00
POLYNT COMPOSITES USA INC.
AUGUSTA, GA—2026-07-16 00:00:00
GF CASTING SOLUTIONS AUGUSTA, LLC
CHAMBLEE, GA—2026-07-16 00:00:00
U.S. DEPARTMENT OF TREASURY
DECATUR, GA—2026-07-15 00:00:00
PALLETS ACQUISITION LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335002788.