BRONX, NY —
OSHA Inspection: LANDO & ASSOCIATES, INC
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of LANDO & ASSOCIATES, INC in 3589 THIRD AVE, BRONX, NY 10456 (NAICS 238220). OSHA activity number 335053203.
Where did this inspection happen?
- Establishment
- LANDO & ASSOCIATES, INC
- Site address
- 3589 THIRD AVE
- City
- BRONX
- State
- NY
- ZIP
- 10456
- Mailing
- 497 WESTBURY AVE, CARLE PLACE, NY 11514
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 2
- Ownership type
- A
Citations
8 citations on file for this inspection.
1926.21 B02
- Issued
- Penalty
- Initial $1020.00 · Current $1020.00
General-duty citation text
29 CFR 1926.21(b)(2): The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury: On or about 6/19/2012, Job Site a) The employees were not provided safety and health training as required by the standard.
Recent events (1)
- — Z (S) $1020
1926.102 A01
- Issued
- Penalty
- Initial $1020.00 · Current $1020.00
General-duty citation text
29 CFR 1926.102(a)(1): Employees shall be provided with eye and face protection equipment when machines or operations present potential eye or face injury from physical, chemical, or radiation agents: On or about 6/19/2012, 1st Floor, D-Area a) The employee was cutting black pipe with a Makita 7 1/4" grinder. He was not using eye and face protection.
Recent events (1)
- — Z (S) $1020
1926.404 B01 I
- Issued
- Penalty
- Initial $1020.00 · Current $1020.00
General-duty citation text
29 CFR 1926.404(b)(1)(i): General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors: On or about 6/19/2012, 1st Floor-D. Area a) The Makita grinder was energized through the temporary powe. The employee was not using a ground fault circuit interrupter.
Recent events (1)
- — Z (S) $1020
1926.404 F06
- Issued
- Penalty
- Initial $1020.00 · Current $1020.00
General-duty citation text
29 CFR 1926.404(f)(6): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent and continuous: On or about 6/19/2012, 1st Floor a) The extension cord had an open ground, exposing the employee to a hazard.
Recent events (1)
- — Z (S) $1020
1926.405 A02 II J
- Issued
- Penalty
- Initial $1020.00 · Current $1020.00
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(J): Extension cord sets used with portable electric tools and appliances shall be of three-wire type and shall be designed for hard or extra-hard usage. Flexible cords used with temporary and portable lights shall be designed for hard or extra-hard usage: NOTE: The National Electrical Code, ANSI/NFPA 70, in Article 400, Table 400-4, lists various types of flexible cords, some of which are noted as being designed for hard or extra-hard usage. Examples of these types of flexible cords include hard service cord (types S, ST, SO, STO) and junior hard service cord (types SJ, SJO, SJT, SJTO). On or about 6/19/2012, 1st Floor a) The employee energized his Makita 7 1/4" grinder with a light duty, 2 conductor extension cord.
Recent events (1)
- — Z (S) $1020
1926.405 B02
- Issued
- Penalty
- Initial $1020.00 · Current $1020.00
General-duty citation text
29 CFR 1926.405(b)(2): Covers and canopies. All pull boxes, junction boxes, and fittings shall be provided with covers. If metal covers are used, they shall be grounded. In energized installations each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear: On or about 6/19/2012, 1st Floor a) The main electrical panel did not have a cover.
Recent events (1)
- — Z (S) $1020
1926.416 E01
- Issued
- Penalty
- Initial $1360.00 · Current $1360.00
General-duty citation text
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables shall not be used: On or about 6/19/2012, 1st Floor a) The 50' extension cord was damaged and laying in water, exposing the employee to an electrical hazard.
Recent events (1)
- — Z (S) $1360
1926.403 G
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.403(g): Marking. Electrical equipment shall not be used unless the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified is placed on the equipment and unless other markings are provided giving voltage, current, wattage, or other ratings as necessary. The marking shall be of sufficient durability to withstand the environment involved: On or about 6/19/2012, 1st Floor a) The Makita skilsaw did not have the proper manufacturer's label.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 238220)
SAN MARCOS, TX—2026-07-16 00:00:00
CASA MECHANICAL SERVICES, LTD.
RIO RANCHO, NM—2026-07-15 00:00:00
PROFESSIONAL STUCCO & SERVICE INC.
BROOKLYN, NY—2026-07-15 00:00:00
DILIGENT AC LLC
PARKVILLE, MD—2026-07-15 00:00:00
AMERICAN AUTOMATIC SPRINKLER COMPANY, INC.
SACRAMENTO, CA—2026-07-15 00:00:00
J.R. PIERCE PLUMBING CO., INC. OF SACRAMENTO
More inspections in NY
MAYVILLE, NY—2026-07-16 00:00:00
MAYVILLE VILLAGE DPW
NEW HYDE PARK, NY—2026-07-16 00:00:00
NORTH HEMPSTEAD TN MICHAEL J TULLY PARK
CONESUS, NY—2026-07-16 00:00:00
CONESUS TN HIGHWAY DEPT
COMSTOCK, NY—2026-07-15 00:00:00
NYSDOCCS WASHINGTON CORRECTIONAL FACILITY
BALDWINSVILLE, NY—2026-07-15 00:00:00
LYSANDER TOWN HIGHWAY DEPARTMENT
Source