Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: JOSEPH J. MOTTES COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of JOSEPH J. MOTTES COMPANY in 10 MEADOW LANE, STAFFORD SPRINGS, CT 06076 (NAICS 327320). OSHA activity number 335237186.

Watch Joseph J. Mottes Company — free Get an email when a new federal OSHA severe-injury report for Joseph J. Mottes Company is published. One employer, no account, unsubscribe in one click.
Site address
10 MEADOW LANE
City
STAFFORD SPRINGS
State
CT
ZIP
06076
Mailing
10 MEADOW LANE, STAFFORD SPRINGS, CT 06076
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327320
Employees
14
Ownership type
A

8 citations on file for this inspection.

1910.147 C06 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(6)(i):   The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:        Building 3, Batch Plant:  On or about December 14, 2012, the employer had not conducted annual inspections of the energy control procedure for the main batch conveyor.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1910.147 C07 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $1000.00
29 CFR 1910.147(c)(7)(i): The training program of the employer did not include all the training elements listed under Items A-C of 29 CFR 1910.147(c)(7)(i):        Building 3, Batch Plant:  On or about December 14, 2012, the employer had not documented that authorized or affected employees had been trained in the elements of the company's lockout/tagout procedures.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $800.00 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:        Building 3, Batch Plant:  On or about December 14, 2012, moving portions on the underside of the main batch conveyor which were less than 8 feet from the ground were not guarded to prevent accidental contact.    Reference:  ANSI B20.1-1993
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.303 G01

Serious Gravity 5 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1000.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:      Building 3, Batch Plant:  On or about December 14, 2012, access to the 480V electrical main panel for the batch conveyor was blocked by the storage of palletized anchor bolts and chemical containers.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.304 A02

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $800.00 Reduced
29 CFR 1910.304(a)(2):   Grounded conductors were attached to terminals or leads so as to reverse designated polarity:      Building 2, Break Room:  On or about December 14, 2012, employees were exposed to electric shock hazards from a Sharp Carousel II microwave oven which was powered through an outlet with reversed polarity.  In this condition, equipment which is turned off is still energized.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.304 G05

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1000.00 Reduced
29 CFR 1910.304(g)(5):  The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:      Building 2, Break Room:  On or about December 14, 2012, employees were exposed to electric shock hazards from the energized metal parts of the Pepsi vending machine.  The equipment was not grounded and the cordset did not have a grounding pin.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.1200 E01

Serious Gravity 5 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $800.00 Reduced
29 CFR 1910.1200(e)(1):   The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:      Facility-wide:  On or about December 14, 2012, the employer had not developed or implemented a written hazard communication program to notify employees of the chemical hazards to which they were exposed, from ready-mix concrete and chemical admixtures.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1910.132 D02

Other-than-serious 1 instance 14 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment:      On or about December 14, 2012, the employer had not certified that a hazard assessment had been completed to determine the type of personal protective equipment required.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View JOSEPH J. MOTTES COMPANY's full OSHA safety record →