Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: NEVADA ARMY NATIONAL GUARD ARMORY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NEVADA ARMY NATIONAL GUARD ARMORY in 151 EAST HORIZON RIDGE PARKWAY FMS#3, HENDERSON, NV 89002 (NAICS 928110). OSHA activity number 336271788.

Watch Nevada Army National Guard Armory — free Get an email when a new federal OSHA severe-injury report for Nevada Army National Guard Armory is published. One employer, no account, unsubscribe in one click.
Site address
151 EAST HORIZON RIDGE PARKWAY FMS#3
City
HENDERSON
State
NV
ZIP
89002
Mailing
CSMS1 - ARMY NATIONAL GUARD, ATTN: DSLOG 2444 FAIRVIEW DR, CARSON CITY, NV 89701
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
10
Ownership type
D

8 citations on file for this inspection.

1910.22 A03

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.22(a)(3): Every floor, working place, and passageway was not kept free from protruding nails, splinters, holes, or loose boards:    a) At the National Guard Armory #FMS building battery shop the metal floor strip to the exit discharge door was bent up on one end a measured height of one inch creating a trip and fall hazard.
Recent events (1)
  • — Z (S) $0

1910.37 A03

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:    a) At the National Guard Armory kitchen, the exit route was obstructed with equipment reducing it to a 22 inch width thereby not meeting the required minimum 28 inch width requirement for exit routes.
Recent events (1)
  • — Z (S) $0

1910.303 B07 IV

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating    a) At the National Guard Armory FMS#3 building a air compressor, model no. Buckeye, Part no. RA1260, had a conduit almost cut in half leading to the electric motor.
Recent events (1)
  • — Z (S) $0

1910.303 G01 VII B

Serious Gravity 5 2 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(vii)(B): The employer did not ensure that outdoor electrical equipment was protected from accidental contact by vehicular traffic.     a) At the National Guard Armory yard, a 600 volt nominal or less panel box enclosure and large upright panel board was located next to a driveway and parking lot and did not protective barriers.
Recent events (1)
  • — Z (S) $0

1910.303 H02 V E

Serious Gravity 1 2 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(h)(2)(v)(E): Doors and covers of enclosures used solely as pull boxes, splice boxes, or junction boxes were not locked, bolted, or screwed on to prevent unauthorized personnel access.     a) At the National Guard Armory yard, a 600 volt nominal or less panel box enclosure door was adjar and did not prevent unauthorized personnel access.
Recent events (1)
  • — Z (S) $0

1910.305 J01 I

Serious Gravity 1 5 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact:    a) At the National Guard Armory, main building main hallway five flourescent dual lamp fixtures at 7 feet 4 inches in height from floor to fixture had lamps removed to conserve energy exposing live parts to employees.
Recent events (1)
  • — Z (S) $0

1910.1200 E01

Other-than-serious 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:    a)  At the National Gaurd Armory, a written Hazard Communication program was not available and chemicals such as acrylic and latex paint, floor wax, cleaners and boiler chemicals were available and in use.
Recent events (1)
  • — Z (O) $0

1910.1200 G08

Other-than-serious 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.1200(g)(8): The employer did not maintain copies of the required material safety data sheets for each hazardous chemical in the workplace:    a) At the main Armory building in the boiler room; Material Safety Data Sheets (MSDS) were not available including but not limited to containers of Glidden and Behr paint, stucco plaster, and Waxie Supergloss floorwax.