HENDERSON, NV —
OSHA Inspection: NEVADA ARMY NATIONAL GUARD ARMORY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NEVADA ARMY NATIONAL GUARD ARMORY in 151 EAST HORIZON RIDGE PARKWAY FMS#3, HENDERSON, NV 89002 (NAICS 928110). OSHA activity number 336271788.
Where did this inspection happen?
- Establishment
- NEVADA ARMY NATIONAL GUARD ARMORY
- Site address
- 151 EAST HORIZON RIDGE PARKWAY FMS#3
- City
- HENDERSON
- State
- NV
- ZIP
- 89002
- Mailing
- CSMS1 - ARMY NATIONAL GUARD, ATTN: DSLOG 2444 FAIRVIEW DR, CARSON CITY, NV 89701
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 10
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.22 A03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.22(a)(3): Every floor, working place, and passageway was not kept free from protruding nails, splinters, holes, or loose boards: a) At the National Guard Armory #FMS building battery shop the metal floor strip to the exit discharge door was bent up on one end a measured height of one inch creating a trip and fall hazard.
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) At the National Guard Armory kitchen, the exit route was obstructed with equipment reducing it to a 22 inch width thereby not meeting the required minimum 28 inch width requirement for exit routes.
Recent events (1)
- — Z (S) $0
1910.303 B07 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating a) At the National Guard Armory FMS#3 building a air compressor, model no. Buckeye, Part no. RA1260, had a conduit almost cut in half leading to the electric motor.
Recent events (1)
- — Z (S) $0
1910.303 G01 VII B
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(vii)(B): The employer did not ensure that outdoor electrical equipment was protected from accidental contact by vehicular traffic. a) At the National Guard Armory yard, a 600 volt nominal or less panel box enclosure and large upright panel board was located next to a driveway and parking lot and did not protective barriers.
Recent events (1)
- — Z (S) $0
1910.303 H02 V E
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(h)(2)(v)(E): Doors and covers of enclosures used solely as pull boxes, splice boxes, or junction boxes were not locked, bolted, or screwed on to prevent unauthorized personnel access. a) At the National Guard Armory yard, a 600 volt nominal or less panel box enclosure door was adjar and did not prevent unauthorized personnel access.
Recent events (1)
- — Z (S) $0
1910.305 J01 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: a) At the National Guard Armory, main building main hallway five flourescent dual lamp fixtures at 7 feet 4 inches in height from floor to fixture had lamps removed to conserve energy exposing live parts to employees.
Recent events (1)
- — Z (S) $0
1910.1200 E01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: a) At the National Gaurd Armory, a written Hazard Communication program was not available and chemicals such as acrylic and latex paint, floor wax, cleaners and boiler chemicals were available and in use.
Recent events (1)
- — Z (O) $0
1910.1200 G08
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not maintain copies of the required material safety data sheets for each hazardous chemical in the workplace: a) At the main Armory building in the boiler room; Material Safety Data Sheets (MSDS) were not available including but not limited to containers of Glidden and Behr paint, stucco plaster, and Waxie Supergloss floorwax.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 928110)
FORT LEE, VA—2026-07-15 00:00:00
U.S. DEPARTMENT OF THE ARMY - FORT LEE
TINKER AFB, OK—2026-07-09 00:00:00
U.S. DEPARTMENT OF DEFENSE, TINKER AIR FORCE BASE
COLUMBIA, SC—2026-07-02 00:00:00
U.S. DEPARTMENT OF VETERANS AFFAIRS
COLUMBIA, SC—2026-07-02 00:00:00
U.S. DEPT OF ARMY
COLUMBIA, SC—2026-07-02 00:00:00
U.S. DEPT OF ARMY
More inspections in NV
RENO, NV—2026-07-17 00:00:00
ADVANCE INSTALLATIONS, INC.
RENO, NV—2026-07-16 00:00:00
DC MASONRY
CARSON CITY, NV—2026-07-16 00:00:00
LT BUILDERS
HENDERSON, NV—2026-07-16 00:00:00
ROADRUNNER DRYWALL CORPORATION
ZEPHYR COVE, NV—2026-07-16 00:00:00
DOLLAR TREE STORES, INC.
Source