OSHA Inspection: NORTHEAST WATER SERVICES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NORTHEAST WATER SERVICES, INC. in 100 TECHNOLOGY WAY, SMITHFIELD, RI 02917 (NAICS 541990). OSHA activity number 336441993.

Watch Northeast Water Services, INC. — free Get an email when a new federal OSHA severe-injury report for Northeast Water Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
100 TECHNOLOGY WAY
City
SMITHFIELD
State
RI
ZIP
02917
Mailing
67 GREEN STREET, FOXBORO, MA 02035
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541990
Employees
4
Ownership type
A

5 citations on file for this inspection.

1910.333 B02

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2):     While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):    Utility Plant: Employees were replacing the UV filters on the Aquafine UV Reactor and exposed to contact with the lamp leads of the UV filters whereby the electrical power source was not locked out.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.333 B02 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2)(i):     The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives:    Establishment: the employer did not develop, document, and utilize safe procedures for the control of electrical energy for the Aquafine UV Reactor.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 F02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1400.00 Reduced
29 CFR 1910.147(f)(2)(i):     When outside servicing personnel were engaged in activities in a facility, the onsite employer and the outside employer did not inform each other of their respective lockout or tagout procedures:    Worksite Utility Plant: Where outside servicing personnel were engaged in servicing the Aquafine UV Reactor, the onsite employer and the outside employer did not inform each other of their respective lockout or tagout procedures for the annual service of the Aquafine UV Reactor.
Recent events (3)
  • — F (S) $1400
  • — C (S) $2800
  • — Z (S) $2800

1910.147 F03 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(f)(3)(i):     A procedure was not utilized to afford the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device when servicing and/or maintenance was performed by a crew, craft:    Worksite, Utilities Plant: Empoyees from different facilities were performing maintenance on the Aquafine UV Reactor whereby group lockout procedures were not utilized.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 C01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(1):     The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:    Establishment: The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections.
Recent events (3)
  • — F (S) $0
  • — C (S) $2800
  • — Z (S) $2800