1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: LIGHT TOWER RENTALS INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of LIGHT TOWER RENTALS INC. in RIG #417, LEASE DENVER UNIT, WELL #3249, 4.1 MILES W OF DENVER CITY, DENVER CITY, TX 79323 (NAICS 532490). OSHA activity number 337094189.

Watch Light Tower Rentals INC. — free Get an email when a new federal OSHA severe-injury report for Light Tower Rentals INC. is published. One employer, no account, unsubscribe in one click.
Site address
RIG #417, LEASE DENVER UNIT, WELL #3249, 4.1 MILES W OF DENVER CITY
City
DENVER CITY
State
TX
ZIP
79323
Mailing
2330 E. I-20 SOUTH SERVICE RD., ODESSA, TX 79766
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
532490
Employees
18
Ownership type
A

1 citation on file for this inspection.

1910.304 G05

Serious Gravity 10 5 instances 18 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $4200.00 Reduced
29 CFR 1910.304(g)(5): The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective:    On or about October 23, 2012, three Whisper-Watt power generators and two Allmand portable light towers not grounded in accordance with NEC (National Electrical Code) Article 250:    1. Generator #869, Whisper-Watt Model #DCA 150 SSCU next to the Toolpusher trailer was grounded 7-inches into the ground.  2. Generator #168, Whisper-Watt Model #DCA 70 USI, Serial # 8800346, behind the Directional Driller trailer was grounded 18-inches into the ground.  3. Allmand portable light tower #1028, Serial #0265MXL12, on the northwest corner of the drill site was grounded 17-inches into the ground.  4. Generator #1304, Whisper-Watt Model #DCA 125 SSIU, Serial # 7510593, on the northwest corner of the drill site was grounded 8-inches into the ground.  5. Allmand portable light tower #989, Serial # 0238MXL12, east side of drill site next the briefing area was grounded 5-inches into the ground.
Recent events (2)
  • — I (S) $4200
  • — Z (S) $7000

View LIGHT TOWER RENTALS INC.'s full OSHA safety record →