SAIPAN, MP —
OSHA Inspection: DKK INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DKK INC. in RENO OF RETAIL SPACE INTO A LAUNDRY BUKIKI ST & GARAPAN RD, GARAPAN, SAIPAN, MP 96950 (NAICS 236220). OSHA activity number 338770464.
Where did this inspection happen?
- Establishment
- DKK INC.
- Site address
- RENO OF RETAIL SPACE INTO A LAUNDRY BUKIKI ST & GARAPAN RD, GARAPAN
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- PO BOX 506003 CHALAN KANOA, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 30
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 B02
- Issued
- Abate by
- Penalty
- Initial $1785.00 · Current $1785.00
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: (a) Inside the building under renovation on or about February 11, 2013, a 4 inch square electrical box was not used as designed to be used as it laid on the floor instead of being mounted on a surface. The box was used to power 220 VAC portable power tools. (b) Inside the building under renovation on or about February 11, 2013, a 2 inch by 4 inch handy box was not used as designed to be used as it was hung by wires from an electrical panel that powered a 110 VAC outlet in the box. The box was designed to be mounted on a surface.
Recent events (1)
- — Z (S) $1785
1926.403 I02 I
- Issued
- Abate by
- Penalty
- Initial $1785.00 · Current $1785.00
General-duty citation text
29 CFR 1926.403(i)(2)(i): Except as required or permitted elsewhere in this subpart, live parts of electric equipment operating at 50 volts or more was not guarded against accidental contact by cabinets or other forms of enclosures, or by any of the following means: (a) Inside the building under renovation on or about February 11, 2013, live buss bars and circuit-breaker terminals were exposed to contact in a 220 VAC electrical panel box. The box was 12 inches wide by 16 inches high, and the bottom was 45 inches from the floor. Employees carried rebar and metal posts for concrete shoring in the area.
Recent events (1)
- — Z (S) $1785
1926.405 J02 I
- Issued
- Abate by
- Penalty
- Initial $1785.00 · Current $1785.00
General-duty citation text
29 CFR 1926.405(j)(2)(i): Receptacles, cord connectors, and attachment plugs were not constructed so that no receptacle or cord connector will accept an attachment plug with a different voltage or current rating than that for which the device is intended: (a) Inside the building under renovation on or about February 11, 2013, outlets rated at a 110 VAC were used to supply 220 VAC to a Dae-Kwong DA/B-25 rebar bender.
Recent events (1)
- — Z (S) $1785
More inspections at DKK INC.
SAIPAN, MP—2012-06-11 00:00:00
DKK INC.
View DKK INC.'s full OSHA safety record →
More inspections in this industry (NAICS 236220)
NEWPORT BEACH, CA—2026-07-16
KPRS CONSTRUCTION SERVICES, INC.
CHANDLER, AZ—2026-07-16
SUN STATE BUILDERS
ROCHESTER HILLS, MI—2026-07-16
ICON RESTORATION SERVICES
WAUSAU, WI—2026-07-16
MIRON CONSTRUCTION CO. INC.
PONCE, PR—2026-07-15
FC CONSTRUCTION LLC
More inspections in MP
SAIPAN, MP—2025-05-15
PARAGON CORP.
SAIPAN, MP—2025-05-14
WINZY CORPORATION
SAIPAN, MP—2025-05-14
HONG YE RENTAL & CONSTRUCTION, LTD.
SAIPAN, MP—2025-05-14
GU LI QIANG
SAIPAN, MP—2025-05-14
GENESIS ENTERPRISES, LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338770464.