PECOS, TX —
OSHA Inspection: LANTERN DRILLING CO.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LANTERN DRILLING CO. in 19.6 MILES SE OF PECOS, PECOS, TX 79772 (NAICS 213111). OSHA activity number 338908577.
Where did this inspection happen?
- Establishment
- LANTERN DRILLING CO.
- Site address
- 19.6 MILES SE OF PECOS
- City
- PECOS
- State
- TX
- ZIP
- 79772
- Mailing
- 8601 N. COUNTY RD WEST, ODESSA, TX 79764
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213111
- Employees
- 200
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $2700.00 · Current $2700.00
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: On or about February 12, 2013, employees were working on Rig # 2 where two electrical boxes had unused openings that were not closed. One was located in front of the company man and tool pusher's trailers on a 480V three phase dry type transformer. The other was located outside the generator room which was used for a 110V battery charger. Employees were exposed to potential electrical hazards.
Recent events (1)
- — Z (S) $2700
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(b)(2)(i): In completed installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass were not provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear: On or about February 12, 2013, employees were working on Rig #2 where an electrical box had a broken faceplate and another electrical box had cords running through a hole that didn't have a bushing. The first was located on a 480V three pahse transformer in front of the tool pusher and company man's trailers. The other was a 480V electrical box in the electrical room. Employees were exposed to potential electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Abate by
- Penalty
- Initial $2700.00 · Current $2700.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Where run through holes in walls, ceilings, or floors: On or about February 12, 2013, employees were working on a Rig # 2. The change room had an electrical cord running through a hole in the metal wall, it was powering a heater from a 220V outlet. Employees were potentially exposed to electrical hazards.
Recent events (1)
- — Z (S) $2700
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws: On or about February 12, 2013, employees were working on Rig #2. An electrical box outside the generator room had a cord running from it to the inside of the room; it was used to power a 110V battery charger. The cord had a damaged strain relief which exposed employees to potential electrical hazards.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 213111)
JAL, NM—2026-07-01 00:00:00
HELMERICH & PAYNE, IDC
LAREDO, TX—2026-06-29 00:00:00
AXIS ENERGY SERVICES, LLC
MCALESTER, OK—2026-06-18 00:00:00
SANGUINE GAS EXPLORATION, LLC
MOUNT PLEASANT, MI—2026-06-15 00:00:00
BIGARD & HUGGARD DRILLING INC
MOUNT PLEASANT, MI—2026-06-15 00:00:00
BIGARD & HUGGARD DRILLING INC
More inspections in TX
WICHITA FALLS, TX—2026-07-16 00:00:00
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16 00:00:00
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15 00:00:00
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15 00:00:00
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15 00:00:00
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338908577.