OSHA Inspection: LANTERN DRILLING CO.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of LANTERN DRILLING CO. in 19.6 MILES SE OF PECOS, PECOS, TX 79772 (NAICS 213111). OSHA activity number 338908577.

Watch Lantern Drilling CO. — free Get an email when a new federal OSHA severe-injury report for Lantern Drilling CO. is published. One employer, no account, unsubscribe in one click.
Site address
19.6 MILES SE OF PECOS
City
PECOS
State
TX
ZIP
79772
Mailing
8601 N. COUNTY RD WEST, ODESSA, TX 79764
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
200
Ownership type
A

4 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 2 instances 15 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $2700.00
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed:  On or about February 12, 2013, employees were working on Rig # 2 where two electrical boxes had unused openings that were not closed. One was located in front of the company man and tool pusher's trailers on a 480V three phase dry type transformer. The other was located outside the generator room which was used for a 110V battery charger. Employees were exposed to potential electrical hazards.
Recent events (1)
  • — Z (S) $2700

1910.305 B02 I

Serious Gravity 5 2 instances 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): In completed installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass were not provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about February 12, 2013, employees were working on Rig #2 where an electrical box had a broken faceplate and another electrical box had cords running through a hole that didn't have a bushing. The first was located on a 480V three pahse transformer in front of the tool pusher and company man's trailers. The other was a 480V electrical box in the electrical room. Employees were exposed to potential electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $2700.00
29 CFR 1910.305(g)(1)(iv)(B): Where run through holes in walls, ceilings, or floors:  On or about February 12, 2013, employees were working on a Rig # 2.  The change room had an electrical cord running through a hole in the metal wall,  it was powering a heater from a 220V outlet. Employees were potentially exposed to electrical hazards.
Recent events (1)
  • — Z (S) $2700

1910.305 G02 III

Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws:  On or about February 12, 2013, employees were working on Rig #2. An electrical box outside the generator room  had a cord running from it to the inside of the room; it was used to power a 110V battery charger. The cord had a damaged strain relief which exposed employees to potential electrical hazards.
Recent events (1)
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338908577.