Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: LAMBARIA ELECTRIC, LLC

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of LAMBARIA ELECTRIC, LLC in 210 TULETA DR, SAN ANTONIO, TX 78212 (NAICS 238210). OSHA activity number 338912116.

Watch Lambaria Electric, LLC — free Get an email when a new federal OSHA severe-injury report for Lambaria Electric, LLC is published. One employer, no account, unsubscribe in one click.
Site address
210 TULETA DR
City
SAN ANTONIO
State
TX
ZIP
78212
Mailing
755 LOOP 337 STE. C, NEW BRAUNFELS, TX 78130
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

3 citations on file for this inspection.

1926.403 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees:  On or about February 13, 2013, employees were exposed to an electrical hazard while working at a temporary power pole which did not have a functioning Ground-Fault interrupter receptacle and missing circuit breaker blanks.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1926.404 B01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:                                                                        On or about February 13, 2013, employees were exposed to an electrical hazard while working at a temporary power pole which did not have a functioning Ground-Fault interrupter receptacle.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1926.405 B01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1296.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:                                   On or about February 13, 2013, employees were exposed to an electrical hazard while working at a temporary power pole which was missing circuit breaker blanks, exposing live parts.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338912116.