Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SHAW ENVIRONMENTAL & INFRASTRUCTURE GROUP

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SHAW ENVIRONMENTAL & INFRASTRUCTURE GROUP in BLDG 788 NAVAL AIR STATION NORTH ISLAND, SAN DIEGO, CA 92136 (NAICS 562920). OSHA activity number 338942949.

Watch Shaw Environmental & Infrastructure Group — free Get an email when a new federal OSHA severe-injury report for Shaw Environmental & Infrastructure Group is published. One employer, no account, unsubscribe in one click.
Site address
BLDG 788 NAVAL AIR STATION NORTH ISLAND
City
SAN DIEGO
State
CA
ZIP
92136
Mailing
1230 COLUMBIA STREET STE 1200, SAN DIEGO, CA 92101
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562920
Employees
45
Ownership type
A

5 citations on file for this inspection.

1910.212 A01

Other-than-serious 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $2550.00 · Current $1275.00 Reduced
29 CFR 1910.212(a)(2)(i): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    Pump P-28A Motor: On or about 07MAR13, a servicing hole seven eighths and inch in diameter was left uncovered on end of the pump motor exposing employees, their clothing or tools, to inadvertent contact with the rotating metal parts inside.
Recent events (2)
  • — I (O) $1275
  • — Z (S) $2550

1910.219 C02 I

Other-than-serious 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $4250.00 · Current $2125.00 Reduced
29 CFR 1910.219(c)(2)(i): Exposed part(s) of horizontal shafting seven (7) feet or less from floor or working platform were not protected by stationary casing(s) enclosing shafting completely or by trough(s) enclosing sides and top or sides and bottom of shafting:    (a) BTF Blower Motor: On or about 07MAR13, the horizontal power transmission shaft of the BTF Blower motor was not fully enclosed in to protect employees, their clothing or tools, from inadvertent contact with the moving shaft.                                                                                           (b) Pump P-34A & B Motors: On or about 07MAR13, the horizontal power transmission shafts of the P-34A & B pump motors were not fully enclosed in to protect employees, their clothing or tools, from inadvertent contact with the moving shafts.    (c) Pump P-28A & B Motors: On or about 07MAR13, the horizontal power transmission shafts of the P-28A & B pump motors were not fully enclosed in to protect employees, their clothing or tools, from inadvertent contact with the moving shafts.
Recent events (2)
  • — I (O) $2125
  • — Z (S) $4250

1910.303 B07 I

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $2550.00 · Current $1275.00 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:    Near T24A Dissolved Air Flotation Unit: On or about 07MAR13, 120VAC live conductors were exposed to inadvertent employee contact where an opening on an electrical box was left uncovered.
Recent events (2)
  • — I (O) $1275
  • — Z (S) $2550

1910.303 B07 III

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $3400.00 · Current $0.00 Reduced
29 CFR 1910.303(b)(7)(iii): Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, may not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues.   T-7 Clarifier Retaining Area: On or about 07MAR13, the employer exposed employees to electrical shock by failing to properly repair or replace an electrical junction box that was cracked with large pieces of the case walls missing; the employer filled the voids and cracks with foreign material consisting of an expanding foam and caulking in lieu of replacing the broken junction box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3400

1910.303 B07 IV

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(iv): There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.  T-7 Clarifier Retaining Area: On or about 07MAR13, the employer exposed employees to electrical shock by failing to properly repair or replace an electrical junction box that was cracked with large pieces of the case walls missing; the employer filled the voids and cracks with foreign material consisting of an expanding foam and caulking in lieu of replacing the broken junction box.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0