TAMPA, FL —
OSHA Inspection: LANZO LINING SERVICES, INC.- FLORIDA
Federal Agency inspection · Health discipline
At a glance
On , OSHA opened a federal Agency health inspection of LANZO LINING SERVICES, INC.- FLORIDA in TAMPA WASTEWATER TREATMENT 2700 MARITIME BLVD, TAMPA, FL 33605 (NAICS 237110). OSHA activity number 339006918.
Where did this inspection happen?
- Establishment
- LANZO LINING SERVICES, INC.- FLORIDA
- Site address
- TAMPA WASTEWATER TREATMENT 2700 MARITIME BLVD
- City
- TAMPA
- State
- FL
- ZIP
- 33605
- Mailing
- 125 SE 5TH COURT, DEERFIELD BEACH, FL 33441
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237110
- Employees
- 14
- Ownership type
- A
Citations
13 citations on file for this inspection.
1910.22 C
- Issued
- Abate by
- Penalty
- Initial $4950.00 · Current $4640.00 Reduced
General-duty citation text
29 CFR 1910.22(c): Covers and/or guardrails were not provided to protect personnel from the hazards of open pits, tanks, vats, ditches, etc. a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees working at the ground level of the 90 degree bend opening leading to meter vault # 2 - building #7 and to sedimentation tanks #5-8 , on or about 4/11/13. Employees were standing at the ground level where the pipe was cut open and were not provided with fall protection to prevent them from falling into the pipe opening; therefore, exposing the employees to an approximate 6 ft fall hazard.
Recent events (2)
- — I (S) $4640
- — Z (S) $4950
1910.146 D03 IV
- Issued
- Abate by
- Penalty
- Initial $6930.00 · Current $6360.00 Reduced
General-duty citation text
29 CFR 1910.146(d)(3)(iv): The employer did not purge, inert, flush, or ventilate the permit space as necessary to eliminate or control atmospheric hazards: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault # 2 - building 7, on or about 4/11/13. Employees entered the confined space without the use of continuous forced air ventilation. The venturi pneumatic air mover was set up at the entrance of the sewer pipe to exhaust air out. The other end of the pipe still had the meter valve in place and was closed, so no forced air ventilation was provided. The pipe was approximately 193 feet long. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe using the ladder near sedimentation tanks #5-8, on or about 4/10/13. Employees entered the confined space without the use of continuous forced air ventilation into the sewer pipe. The venturi pneumatic air mover was set up at the top of the ladder and forced air down in front of the opening but did not force air into the horizontal pipe where the employee walked approximately 5- 20 ft.
Recent events (2)
- — I (S) $6360
- — Z (S) $6930
1910.146 D08
- Issued
- Abate by
- Penalty
- Initial $6930.00 · Current $6360.00 Reduced
General-duty citation text
29 CFR 1910.146(d)(8): Under the permit-required confined space program required by 29 CFR 1910.146(c)(4), the employer did not designate the persons who were to have active roles in entry operations, identify the duties of each such employee, and did not provide each such employee with training required by paragraph (g) of this section: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault # 2 - building #7, on or about 4/11/13. Employees entered the confined space without designating the persons who were to have active roles, such as, but not limited to, entry supervisor, attendants, entrants and air tester. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to sedimentation tanks #5-8, on or about 4/11/13. Employees entered the confined space without designating the persons who were to have active roles, such as, but not limited to, entry supervisor and air tester. c. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe using the ladder near sedimentation tanks #5-8, on or about 4/10/13. Employees entered the confined space without designating the persons who were to have active roles, such as, but not limited to, entry supervisor, attendants and air tester.
Recent events (2)
- — I (S) $6360
- — Z (S) $6930
1910.146 E01
- Issued
- Penalty
- Initial $6930.00 · Current $6360.00 Reduced
General-duty citation text
29 CFR 1910.146(e)(1): Before entry was authorized, the employer did not document the completion of measures required by 29 CFR 1910.146(d)(3) by preparing an entry permit: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault #2 - building #7, on or about 4/11/13. Employees entered the confined space without the completion of an entry permit. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe using the ladder near sedimentation tanks # 5-8, on or about 4/10/13. An employee carried a 4" vacuum hose approximately 5- 20 ft inside the pipe to pump out water.
Recent events (2)
- — I (S) $6360
- — Z (S) $6930
1910.146 F06
- Issued
- Abate by
- Penalty
- Initial $6930.00 · Current $6360.00 Reduced
General-duty citation text
29 CFR 1910.146(f)(6): The entry permit that documented compliance and authorized entry to a permit space did not identify the individual, by name, currently serving as entry supervisor, with a space for the signature or initials of the entry supervisor who originally authorized entry: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault #2 - building #7, on or about 4/11/13. Employees entered the confined space without identifying the name of the person serving as the entry supervisor.
Recent events (2)
- — I (S) $6360
- — Z (S) $6930
1910.146 F10
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.146(f)(10): The entry permit that documented compliance and authorized entry to a permit space did not identify the results of initial and periodic tests performed under 29 CFR 1910.146(d)(5), accompanied by the names or initials of the tester: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault #2 -building #7, on or about 4/11/13. Employees entered the confined space without the atmospheric test results documented on the entry permit. This section of pipe was not provided with forced air ventilation. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to sedimentation tanks #5-8, on or about 4/11/13. Employees worked in the permit required confined space for approximately 4 hours. Periodic atmospheric conditions were not recorded. Exit atmospheric conditions were not recorded on the entry permit. c. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a vertical confined space entry at Junction Chamber #2, on or about 4/9/13. Employees re-entered the confined space at 10:30 am without documentation of atmospheric test results on the entry permit. The employee exited at 11:05 am without exit readings documented on the entry permit. The entry permit lists the last exit reading at 9:02 am which is before the re-entry occurred. d. Howard F. Curren Advanced Wastewater Treatment Plant - for atmospheric readings at the opening to the pipe section leading to sedimentation tanks # 5-8, on or about 4/9/13. A 4-gas meter was lowered into the ladder opening and was used to measure the atmospheric conditions at approximately 12:05 pm at opening. The hydrogen sulfide levels were high and caused the gas meter alarm to activate. When the alarm activated the entry permit was voided; however, the atmospheric levels were not recorded on the entry permit to inform employees of the dangerous levels.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.146 K01 I
- Issued
- Abate by
- Penalty
- Initial $6930.00 · Current $6360.00 Reduced
General-duty citation text
29 CFR 1910.146(k)(1)(i): An employer who designated rescue and emergency services, pursuant to paragraph (d)(9) of this section, did not evaluate a prospective rescuer's ability to respond to a rescue summons in a timely manner, considering the hazard(s) identified: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter building and the opening leading to sedimentation tanks #5-8, on or about 4/11/13. The entry permits identified emergency rescue numbers as "911"; however, the employer did not coordinate and/or evaluate the prospective rescuer's ability to perform rescue. Employees were exposed to hydrogen sulfide gas. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe using the ladder near the sedimentation tanks to enter the confined space to install a vacuum hose on or about 4/10/13. The entry permits identified emergency rescue numbers as "911"; however, the employer did not coordinate and/or evaluate the prospective rescuer's ability to perform rescue. Employees were exposed to hydrogen sulfide gas. c. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a vertical confined space entry into the junction chamber to work with the stop logs, on or about 4/9/13. The entry permits identified emergency rescue numbers as "911"; however, the employer did not coordinate and/or evaluate the prospective rescuer's ability to perform rescue. Employees were exposed to hydrogen sulfide gas.
Recent events (2)
- — I (S) $6360
- — Z (S) $6930
1910.146 K03 II
- Issued
- Abate by
- Penalty
- Initial $6930.00 · Current $6360.00 Reduced
General-duty citation text
29 CFR 1910.146(k)(3)(ii): An authorized entrant entered a permit space and did not have the other end of the retrieval line attached to a mechanical device or fixed point outside the permit space in such a manner that rescue could begin as soon as the rescuer becomes aware that rescue is necessary: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to sedimentation tanks #5-8, on or about 4/11/13. An employee entered the confined space wearing a harness and rope. The rope was not attached to a mechanical device or a fixed point outside the permit space.
Recent events (2)
- — I (S) $6360
- — Z (S) $6930
1910.146 D05 I
- Issued
- Abate by
- Penalty
- Initial $69300.00 · Current $63600.00 Reduced
General-duty citation text
29 CFR 1910.146(d)(5)(i): Test conditions in the permit space to determine if acceptable entry conditions exist before entry is authorized to begin, except that, if isolation of the space is infeasible because the space is large or is part of a continuous system (such as a sewer), pre-entry testing shall be performed to the extent feasible before entry is authorized and, if entry is authorized, entry conditions shall be continuously monitored in the areas where authorized entrants are working; a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault #2 - building #7, on or about 4/11/13. Employees were exposed to hydrogen sulfide gas, in that, a gas detector was not used to determine the internal atmosphere at the location where employees were conducting cleaning activities. Employees were working approximately 125 ft inside the sewer pipe. One employee died and another employee was hospitalized due to hydrogen sulfide overexposure. Forced air ventilation was not provided. In addition, two other employees were working up to 20 ft inside the sewer pipe without using a gas detector. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to sedimentation tanks #5-8, on or about 4/11/13. Employees were exposed to hydrogen sulfide gas, in that, a gas detector was not used to determine the internal atmosphere at the location where employees were conducting cleaning activities. Employees were working up to approximately 140 feet inside the sewer pipe. The 90 degree bend was open to the outside atmosphere. A venturi pneumatic air mover (bazooka) was placed at the entrance to the pipe to blow (supply) air. The other end of the pipe was open to the atmosphere (sedimentation tanks). Another pneumatic air mover was placed at the ladder to exhaust air out of the space. The bazooka was placed near the top of the 10-12 ft ladder. A Gas Alert Max XT meter (serial #MA211-037024) was placed at the entrance of the 90 degree bend; however, employees did not have a gas detector at the location of work inside the sewer pipe. c. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to sedimentation tanks #5-8, on or about 4/10/13. Employees were exposed to hydrogen sulfide gas, in that, a gas detector was not used to determine the internal atmosphere at the location where an employee carried the vacuum hose approximately 5- 20 ft into the sewer pipe. The 90 degree bend was closed to the outside atmosphere. A Gas Alert Max XT meter (serial #MA211-037024) was lowered down the vertical ladder and was hung at approximately 5' - 5'-5" high from the bottom of the pipe.; however, employees did not have a gas detector at the location of work.
Recent events (2)
- — I (R) $63600
- — Z (W) $69300
1910.146 K03 I
- Issued
- Abate by
- Penalty
- Initial $69300.00 · Current $63600.00 Reduced
General-duty citation text
29 CFR 1910.146(k)(3)(i): Each authorized entrant did not use a chest or full body harness, with a retrieval line attached at the center of the entrant's back near shoulder level, or above the entrant's head, or at another point which the employer can establish presents a profile small enough for the successful removal of the entrant. Wristlets may be used in lieu of the chest or full body harness if the employer can demonstrate that the use of a chest or full body harness is infeasible or creates a greater hazard and that the use of wristlets is the safest and most effective alternative: a. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to sedimentation tanks #5-8, on or about 4/11/13. Two employees entered the confined space without wearing a harness and retrieval line. b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault #2 - building #7, on or about 4/11/13. Three employees entered the confined space without wearing a harness and retrieval line. Two employees became unconscious due to overexposure to hydrogen sulfide gas at approximately 125 ft inside the sewer pipe. No retrieval system was in use to remove employees from the hazardous environment. One employee died. Six rescuers also went inside the confined space without a harness and retrieval line.
Recent events (2)
- — I (R) $63600
- — Z (W) $69300
1910.132 D02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment: a. Howard F. Curren Advanced Wastewater Treatment Plant - the employer did not develop a written certification for the workplace hazard assessment. Violation observed on or about 4/22/13.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.134 E01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: a. Howard F. Curren Advanced Wastewater Treatment Plant - employees fit tested and provided with half-face and full-face respirators were not provided with a medical evaluation to determine the employee's ability to wear a respirator. Violation observed on or about 06/28/13.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.146 C02
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.146(c)(2): The employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces: b. Howard F. Curren Advanced Wastewater Treatment Plant - for employees conducting a horizontal confined space entry into an 8 ft diameter sewer pipe through the 90 degree bend opening leading to meter vault #2 - building #7 and the opening leading to sedimentation tanks #5-8, on or about 4/11/13. The employer did not post danger signs identifying the confined space as a permit required confined space.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 237110)
COLUMBIA, PA—2026-07-17 00:00:00
FOX TAPPING INC.
POUND, VA—2026-07-17 00:00:00
TRAXON CONSTRUCTION INC.
GREEN BAY, WI—2026-07-17 00:00:00
PTS CONTRACTORS, INC.
SWISSVALE, PA—2026-07-16 00:00:00
S&E UTILITY CONTRACTING, INC.
MINNEAPOLIS, MN—2026-07-16 00:00:00
111607 - PCIROADS LLC
More inspections in FL
DELAND, FL—2026-07-16 00:00:00
BALL FABRICS
GAINESVILLE, FL—2026-07-16 00:00:00
WACKY SAUCES LLC
FORT WALTON BEACH, FL—2026-07-16 00:00:00
WASTE MANAGEMENT, INC. OF FLORIDA
PONCE INLET, FL—2026-07-16 00:00:00
RESOLUTE ROOFING LLC
PALM COAST, FL—2026-07-16 00:00:00
J & J TREE EXPERTS, INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339006918.