Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: KRAFT FOODS GLOBAL

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of KRAFT FOODS GLOBAL in 7 HILL STREET, WOBURN, MA 01801 (NAICS 311999). OSHA activity number 339230104.

Watch Kraft Foods Global — free Get an email when a new federal OSHA severe-injury report for Kraft Foods Global is published. One employer, no account, unsubscribe in one click.
Establishment
KRAFT FOODS GLOBAL
Site address
7 HILL STREET
City
WOBURN
State
MA
ZIP
01801
Mailing
7 HILL STREET, WOBURN, MA 01801
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311999
Employees
240
Ownership type
A

12 citations on file for this inspection.

1910.23 C01

Serious Gravity 10 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $3000.00 Reduced
29 CFR 1910.23(c)(1): Every open-sided floor or platform 4 feet or more above adjacent floor or ground level shall be guarded by a standard railing (or the equivalent as specified in paragraph (e)(3) of this section) on all open sides except where there is entrance to a ramp, stairway, or fixed ladder. The railing shall be provided with a toeboard wherever, beneath the open sides,    (a) Location - Roof of the Steam Plant:  On or about 7/24/13, the employer did not ensure the employees were protected from falling greater than 4 feet to a lower level.      (b) Location - Pig Dock area, Crane Bay 1:  On or about 7/24/13, the employer did not ensure employees were protected from falling greater than 4 feet to a lower level.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $7000

1910.137 B02 VIII

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $1500.00 Reduced
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:    (a) Location - Hall Road, Woburn, MA:  On or about 7/24/2013, the employer failed to ensure that the rubber insulating gloves were inspected every six (6) months.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $7000

1910.147 C06 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4400.00 · Current $2000.00 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:    (a) Location - 7 Hill Street, Woburn, MA:   On or about 7/24/13, the employer failed to perform an annual evaluation on its lockout/tagout program.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $4400

1910.178 N06

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.178(n)(6): Industrial truck drivers were not required to look in the direction of, and keep a clear view of the path of travel:  (a)    Location - Hill Road, Woburn, MA, Pig Dock, Shipping and Receiving Area: On or about 7/24/13, the  employer failed to ensure employees were looking in the direction of travel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.184 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $2000.00 Reduced
29 CFR 1910.184(e)(1): Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach:    (a) Location: Hill Road, Woburn, MA  On or about 7/24/13, employees were exposed to crushing hazards when employer failed to ensure that permanently affixed durable identification tags were attached to alloy steel chains.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $4000

1910.184 E03 I

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.184(e)(3)(i): A thorough periodic inspection of alloy steel chain slings was not made on a regular basis and/or were done at intervals greater than once every 12 months:    (a) Location - Hill Road, Woburn, MA:  On or about 7/24/13, the employer failed to provided annual inspections of the alloy steel chain slings.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A01

Serious Gravity 10 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $2500.00 Reduced
29 CFR 1910.212(a)(1): Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices,electronic safety devices, etc.    (a) Location - Emulsion Room:  On or about 7/24/13, the employer failed to adequately guard the adjustable height for the pail filler in the Emulsion Room.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $7000

1910.219 D01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $0.00 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):(a) (LOCATION) (IDENTIFY SPECIFIC OPERATION(S) AND/OR CONDITIONS) (DESCRIBE HAZARD(S) WHERE NECESSARY)    (a) Location - Hill Street, Woburn, MA:  On or about 7/24/2013, the employer failed to adequately guard the conveyors.  The employees were moving within inches of the exposed pulleys on the Box Machine conveyor.    (b) Location - Hill Street, Woburn, MA:  On or about 7/24/2013, the employer failed to guard the gears on the Remount Machine near Mepaco.    (c) Location - Hill Street, Woburn, MA;  On or about 7/24/2013, the employer failed to guard the belt driven pulley on the Palletizer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.303 B07 IV

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $6000.00 · Current $2500.00 Reduced
29 CFR 1910.303(b)(7)(iv): There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.    (a) Location - Hill Road, Woburn, MA  On or about 7/24/2013, the employer failed to repair a damaged cord on a hand grinder.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $6000

1910.303 G01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $1500.00 Reduced
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:(a) (LOCATION) (IDENTIFY EQUIPMENT AND CONDITION(S)) (STATE HAZARD(S) TO EMPLOYEE(S) AND SPECIFY DISTANCE REQUIRED)    (a) Steam Power Building, upper level:  On or about 7/24/2013, there were structural impediments that would limit an electrician to approximately 12 inches of access at the electrical boxes.      (b) Near the Bagger area:  On or about 7/24/2013, there were structural impediments that would limit an electrician to approximately 12 inches of access at the electrical boxes.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $7000

1910.305 J01 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $4000.00 · Current $0.00 Reduced
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals.  (a) Power Plant On or about 7/24/2013, the employer failed to ensure the light fixture in the power station was protected by a guard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4000

1910.304 F01 VIII

Deleted Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits shall be listed and marked "SWD."  (a) Location - Hill Road, Woburn, MA: On or about 7/24/2013, the employer failed to ensure that a circuit breaker being used as a switch when changing the florescent lighting circuit was approved and marked "SWD."
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View KRAFT FOODS GLOBAL's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339230104.