WAUKESHA, WI —
OSHA Inspection: PET WORLD, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PET WORLD, INC. in 2410 E. MORELAND BLVD., WAUKESHA, WI 53186 (NAICS 453910). OSHA activity number 339439937.
Where did this inspection happen?
- Establishment
- PET WORLD, INC.
- Site address
- 2410 E. MORELAND BLVD.
- City
- WAUKESHA
- State
- WI
- ZIP
- 53186
- Mailing
- 2410 E. MORELAND BLVD., WAUKESHA, WI 53186
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 453910
- Employees
- 24
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.305 J02 IV
- Issued
- Abate by
- Penalty
- Initial $6300.00 · Current $3780.00 Reduced
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: (a) The employer did not ensure that outlet boxes located in the utility room were approved for operation in wet environments. The employees were exposed to electrical shock hazards.
Recent events (2)
- — I (S) $3780
- — Z (S) $6300
1910.334 A04
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.334(a)(4): Portable electric equipment and flexible cords that was used in highly conductive work locations (such as those inundated with water or other conductive locations) or in job locations where employees were likely to contact water or conductive liquids were not approved for those locations. (a) The employer did not ensure that outlet boxes located in the utility room were approved for operation in wet environments. The employees were exposed to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1200 H01
- Issued
- Abate by
- Penalty
- Initial $2700.00 · Current $1620.00 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: (a) The employer did not ensure that employees were effectively trained in hazardous chemicals. The employees were exposed to chemical hazards.
Recent events (2)
- — I (S) $1620
- — Z (S) $2700
1910.303 E
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(e): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary: (a) The employer did not ensure that electrical panels were marked with electrical information as specificed in this standard. The employees were exposed to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 I A
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: (a) The employer did not ensure that the depth in front of electrical panels and disconnect boxes were clear. The employees were exposed to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 I B
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : (a) The employer did not ensure that the width in front of electrical panels and disconnect boxes were clear. The employees were exposed to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at PET WORLD, INC.
WAUKESHA, WI—2012-03-02 00:00:00
PET WORLD, INC.
View PET WORLD, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 453910)
MONROVIA, CA—2026-05-28
PETSMART
CRESTWOOD, IL—2026-04-17
PETSMART LLC
PORTLAND, OR—2026-03-30
317743497 - WESTERN PET SUPPLY INC
NORTH RIVERSIDE, IL—2026-03-26
PETCO ANIMAL SUPPLIES STORES, INC.
VERADALE, WA—2026-03-25
WA317990437 - PETCO ANIMAL SUPPLIES STORES INC
More inspections in WI
MUSCODA, WI—2026-07-10
SCOT INDUSTRIES, INC
FRANKLIN, WI—2026-07-10
EDGE BROADBAND SOLUTIONS LLC
APPLETON, WI—2026-07-10
LAWRENCE UNIVERSITY OF WISCONSIN
KIMBERLY, WI—2026-07-10
ENRIQUE RESENDIC
SLINGER, WI—2026-07-10
DYLAN MATTHEW SHELLEY LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339439937.