BLACK RIVER FALLS, WI —
OSHA Inspection: MEISTERS FOREST PRODUCTS
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of MEISTERS FOREST PRODUCTS in 700 TIMBER ROAD, BLACK RIVER FALLS, WI 54615 (NAICS 321113). OSHA activity number 339534315.
Where did this inspection happen?
- Establishment
- MEISTERS FOREST PRODUCTS
- Site address
- 700 TIMBER ROAD
- City
- BLACK RIVER FALLS
- State
- WI
- ZIP
- 54615
- Mailing
- 700 TIMBER ROAD, BLACK RIVER FALLS, WI 54615
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321113
- Employees
- 20
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.147 C05 II D
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1960.00 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(ii)(D): Lockout devices and tagout devices did not indicate the identity of the employee applying the device(s): (a) Throughout the production area; The identity of employee(s) performing servicing and maintenance operations on locked out equipment was not indicated on the lockout or tagout devices. i. Fastline brand edger ii. Morbark brand Chipper
Recent events (3)
- — F (S) $1960
- — C (S) $2800
- — Z (S) $2800
1910.147 D04 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees: (a) Production area; Energy isolation devices were not used during servicing and maintenance operations such as, but not limited to, changing blades, clearing jams, sharpening blades, and cleaning. i. Scragg saw ii. Horizontal scragg saw iii. Outside edger iv. Baker 5 head bandsaws
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.147 F03 II D
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.147(f)(3)(ii)(D): Each authorized employee did not affix a personal lockout or tagout device to the group lockout device before working on the machine or equipment: (a) Throughout the facility; Lockout devices were not applied by each employee who changed knifes on the chipper when it was locked out.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.265 C18 I
- Issued
- Abate by
- Penalty
- Initial $1600.00 · Current $1120.00 Reduced
General-duty citation text
29 CFR 1910.265(c)(18)(i): Conveyor(s) installed within 7 feet of the floor or walkway surface were not provided with crossover(s) or passageway(s) or with telltales indicating low headroom (Reference: American National Standard B20.1-1957, Section 705.a): (a); Production area; Crossovers were not provided for crossing over belt and vibrating style conveyors. i. Inside Double-end trim saw station ii. Outside Double-end trim saw station
Recent events (3)
- — F (S) $1120
- — C (S) $1600
- — Z (S) $1600
1910.265 E04 II A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.265(e)(4)(ii)(a): Trimmer saw(s) were not guarded in front by adequate baffles to protect against flying debris: (a) Outside Double-end trim saw station; A front side baffle/debris guard was not installed on the right side.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $1400.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) Inside stacker line, conveyor controls; Protection was not provided for exposed conductors on a 120 volt flexible cord.
Recent events (3)
- — F (S) $1400
- — C (S) $2000
- — Z (S) $2000
1910.305 G01 IV
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv): (a) Outside edger; A flexible cord and plug set was used in place of permanent wiring for a permanently mounted 120 volt junction box.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) Inside stacker line, conveyor controls; Strain relief was not provided for 120 volt on/off controls.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1904.32 A03
- Issued
- Abate by
- Penalty
- Initial $400.00 · Current $280.00 Reduced
General-duty citation text
29 CFR 1904.32(a)(3): The employer did not certify an OSHA 300A Form or equivalent. (a) Throughout the facility at 700 Timber Road in Black River Falls, WI; On or about December 30, 2013, the employer failed to certify the annual summary of work-related injuries and illnesses.
Recent events (3)
- — F (O) $280
- — C (O) $400
- — Z (O) $400
1904.32 B02 II
- Issued
- Abate by
- Penalty
- Initial $400.00 · Current $280.00 Reduced
General-duty citation text
29 CFR 1904.32(b)(2)(ii): 29 CFR 1904.32(b)(2)(ii): The employer did not enter the calendar year covered, the company's name, establishment name, establishment address, annual average number of employees covered by the OSHA 300 Log, and the total hours worked by all employees covered by the OSHA 300 Log. (a) Throughout the facility; The total number of hours worked was not written on the annual summary on injury and illness logs (OSHA form 300-A).
Recent events (3)
- — F (O) $280
- — C (O) $400
- — Z (O) $400
1910.95 D01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.95(d)(1): When information indicated that any employee's exposure equaled or exceed the 8-hour time-weighted average of 85 decibels, the employer did not develop and implement a monitoring program: (a) Throughout the facility; The employer did not implement a noise monitoring program. Noise exposure levels were 97.9 to 99.3 dBA.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 321113)
COCHRANTON, PA—2026-07-15 00:00:00
CRAWFORD COUNTY HARDWOODS, LLC
COCHRANTON, PA—2026-07-15 00:00:00
CRAWFORD COUNTY HARDWOODS, LLC
LIVE OAK, FL—2026-07-09 00:00:00
BINDERHOLZ LIVE OAK LLC
LAFAYETTE, TN—2026-07-08 00:00:00
CLARK LUMBER COMPANY, LLC
GASTON, OR—2026-07-07 00:00:00
317744699 - STIMSON LUMBER COMPANY
More inspections in WI
WAUSAU, WI—2026-07-16 00:00:00
MIRON CONSTRUCTION CO. INC.
ELROY, WI—2026-07-15 00:00:00
WABASH NATIONAL SERVICES, L.P.
SUSSEX, WI—2026-07-15 00:00:00
KINGS SUPERIOR CONSTRUCTION LLC
DELAVAN, WI—2026-07-15 00:00:00
TERONOMY BUILDERS, INC.
DELAVAN, WI—2026-07-15 00:00:00
A. GOMEZ CARPENTRY, INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339534315.