Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EXXONMOBIL PRODUCTION COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EXXONMOBIL PRODUCTION COMPANY in 14 MILES WEST OF KINGSVILLE ON HWY 141 KING RANCH GAS PLANT, KINGSVILLE, TX 78364 (NAICS 211112). OSHA activity number 339640625.

Watch Exxonmobil Production Company — free Get an email when a new federal OSHA severe-injury report for Exxonmobil Production Company is published. One employer, no account, unsubscribe in one click.
Site address
14 MILES WEST OF KINGSVILLE ON HWY 141 KING RANCH GAS PLANT
City
KINGSVILLE
State
TX
ZIP
78364
Mailing
P.O. BOX 1150, KINGSVILLE, TX 78364
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
211112
Employees
76
Ownership type
A

5 citations on file for this inspection.

1910.119 D03 I F

Other-than-serious 3 instances 7 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $1000.00 Reduced
29 CFR 1910.119(d)(3)(i)(F): Information pertaining to the equipment in the process did not include design codes and standards employed;    At the ExxonMobil King Ranch facility located in Kingsville, Texas, in the Refrigerated Absorption De-Methanization Unit,  the employer did not document the design codes and standards employed for the following pieces of equipment:    A.    Compressor 301A control systems, and;     b.    Compressor 306 control systems.
Recent events (3)
  • — F (O) $1000
  • — C (S) $7000
  • — Z (S) $7000

1910.119 D03 I H

Deleted Serious Gravity 10 1 instance 7 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.119(d)(3)(i)(H): The employer did not document information pertaining to safety systems (e.g. interlocks, detection or suppression system).   At the ExxonMobil King Ranch facility located in Kingsville, Texas, in the Refrigerated Absorption De-Methanization Unit, the employer did not ensure the Process Safety Information (PSI) including but not limited to, safety specification requirements were compiled and complete for the safety interlock shutdown systems on the Refrigeration Compressor #306 and Refrigeration Compressor #301A.                                                                                                                                 In the Alternative   29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.  At the ExxonMobil King Ranch facility located in Kingsville, Texas, in the Refrigerated Absorption De-Methanization Unit, the employer did not document safety specification requirements for the safety interlock shutdown systems on the Refrigeration Compressor #306 and Refrigeration Compressor #301A to comply with recognized and generally accepted good engineering practices such as ISA 84.00.01-2004 Part 1 (IEC 61511-1 Mod) Section 10.3.1.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 J04 I

Serious Gravity 5 2 instances 6 exposed
Issued
Abate by
Penalty
Initial $5000.00 · Current $5000.00
29 CFR 1910.119(j)(4)(i): Inspection and tests shall be performed on process equipment.    At the ExxonMobil King Ranch facility located in Kingsville, Texas, in the Refrigerated Absorption De-Methanization Unit; the employer did not ensure an analysis was performed to confirm that there was no impact on the protective system from the changes implemented in MOC#201202042.
Recent events (3)
  • — F (S) $5000
  • — C (S) $5000
  • — Z (S) $5000

1910.119 J04 IV

Other-than-serious 1 instance 7 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that had been performed on process equipment.    At ExxonMobil King Ranch Gas Plant (KRGP) located in Kingsville, Texas, in the Refrigeration and De-Methanization Unit (RADU), the employer did not document and maintain test records for the inspection of the Low Level Shutdown (LLSD) for Lean Oil Still B that occurred on or about September 25, 2013.
Recent events (3)
  • — F (O) $0
  • — C (S) $0
  • — Z (S) $0

1910.119 J05

Serious Gravity 10 2 instances 10 exposed
Issued
Abate by
Penalty
Initial $70000.00 · Current $5000.00 Reduced
29 CFR 1910.119(j)(5): Equipment deficiencies. The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation.      At ExxonMobil King Ranch Gas Plant (KRGP) located in Kingsville, Texas, the employer failed to document that affected piping supports on the 24" Cold Flare header piping system, north of the Refrigeration Absorption De-Methanization Unit were structurally adequate for their intended purpose.
Recent events (3)
  • — F (S) $5000
  • — C (W) $70000
  • — Z (W) $70000