DEER PARK, TX —
OSHA Inspection: SHELL OIL PRODUCTS COMPANY LLC
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of SHELL OIL PRODUCTS COMPANY LLC in 5900 HIGHWAY 225, DEER PARK, TX 77536 (NAICS 324110). OSHA activity number 339841231.
Where did this inspection happen?
- Establishment
- SHELL OIL PRODUCTS COMPANY LLC
- Site address
- 5900 HIGHWAY 225
- City
- DEER PARK
- State
- TX
- ZIP
- 77536
- Mailing
- P O BOX 100, DEER PARK, TX 77536
What kind of inspection was it?
- Inspection type
- Programmed Related (J)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 1100
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.119 J02
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): Written procedures. The employer shall establish and implement written procedures to maintain the on-going integrity of process equipment. On or about June 07, 2014, and times thereto, and possibly times thereafter, at the Shell Oil products facility in Deer Park, Texas, the employer and the designated contractor failed to develop and implement written procedures for performing the task of Rodding-Out process equipment and instrumentation in the Distillation Unit 2.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.132 A
- Issued
- Abate by
- Penalty
- Initial $5000.00 · Current $5000.00
General-duty citation text
29 CFR 1910.132(a): Application. Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, shall be provided, used, and maintained in a sanitary and reliable condition wherever it is necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact: a) On or about June 07, 2014, and at prior times, at the Shell Oil products facility in Deer park Texas, the employer failed to ensure that protective equipment, such as protective shields or barriers and/or thermal protective clothing, were used when an employee opened process equipment operating at 650-700 degree F. b) On or about June 07, 2014, the employer failed to ensure that an employee wore appropriate face and eye protection while opening process equipment operating at 650 to 700 degree F.
Recent events (2)
- — I (S) $5000
- — Z (S) $5000
1910.133 A01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.133(a)(1): The employer did not ensure that each affected employee uses appropriate eye or face protection when exposed to eye or face hazards from flying particles, molten metal, liquid chemicals, acids or caustic liquids, chemical gases or vapors, or potentially injurious light radiation: On or about June 07, 2014, and times thereto, at the Shell Oil products facility in Deer Park, Texas, the employer did not ensure employees wore appropriate face and eye protection while opening process equipment operating at approximately 65-700 deg F.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 D05 I
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.147(d)(5)(i): Following the application of lockout or tagout devices to energy isolating devices, all potentially hazardous stored or residual energy shall be relieved, disconnected, restrained, and otherwise rendered safe: On or about June 07, 2014, and at prior times, at the Shell Oil products facility in Deer park Texas, the employer did not ensure that all stored or residual energy was relieved, restrained or rendered safe prior to performing maintenance work or instrument taps and process flow transmitters.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.119 M03
- Issued
- Abate by
- Penalty
- Initial $1000.00 · Current $1000.00
General-duty citation text
29 CFR 1910.119(m)(3): An incident investigation team shall be established and consist of at least one person knowledgeable in the process involved, including a contract employee if the incident involved work of the contractor, and other persons with appropriate knowledge and experience to thoroughly investigate and analyze the incident: On or about June 07, 2014, and times thereafter, at the Shell Oil products facility in Deer Park, Texas, the employer failed to establish an incident investigation team that consisted of a contract employee when the incident involved the work of the contractor.
Recent events (2)
- — I (O) $1000
- — Z (O) $1000
More inspections at SHELL OIL PRODUCTS COMPANY LLC
DEER PARK, TX—2019-10-17 00:00:00
SHELL OIL PRODUCTS COMPANY LLC
View SHELL OIL PRODUCTS COMPANY LLC's full OSHA safety record →
More inspections in this industry (NAICS 324110)
TORRANCE, CA—2026-07-15
TORRANCE REFINING COMPANY LLC
EL SEGUNDO, CA—2026-06-30
CHEVRON U.S.A. INC.
EL SEGUNDO, CA—2026-06-30
CHEVRON U.S.A. INC.
TRAINER, PA—2026-06-26
MONROE ENERGY, LLC
RICHMOND, CA—2026-06-17
CHEVRON U.S.A. INC.
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339841231.