1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: SEARS, ROEBUCK & CO.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SEARS, ROEBUCK & CO. in 98-180 KAMEHAMEHA, AIEA, HI 96701 (NAICS 452111). OSHA activity number 339897845.

Watch Sears, Roebuck & CO. — free Get an email when a new federal OSHA severe-injury report for Sears, Roebuck & CO. is published. One employer, no account, unsubscribe in one click.
Site address
98-180 KAMEHAMEHA
City
AIEA
State
HI
ZIP
96701
Mailing
3333 BEVERLY ROAD ALL-338A, HOFFMAN ESTATES, IL 60179
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
452111
Employees
200
Ownership type
A

5 citations on file for this inspection.

1910.23 C01

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4250.00 · Current $0.00 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:Note:  Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard:      a. On August 7, 2014 and times prior thereto, on the roof of building, employees walked the perimeter of the roof to inspect and clean the drains and were not provided a personal fall arrest system.
Recent events (2)
  • — I (O) $0
  • — Z (S) $4250

1910.36 G02

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  a. On August 12, 2014, in the storage area, the employer did not maintain the minimum width requirement for an exit route at all points.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.137 B02 VIII

Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:  a. On August 15, 2014, tool room area, the employer did not ensure that rubber insulating gloves were subjected to periodic electrical tests.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a. On August 12. 2014, in the storage area, electrical panel H2C was not legibly marked for to indicate each branch circuit's purpose.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:     a. On August 12, 2014, in the storage room, clothing racks were stored in front of an electrical panel.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View SEARS, ROEBUCK & CO.'s full OSHA safety record →