OSHA Inspection: NOVOTEC RECYCLING

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of NOVOTEC RECYCLING in 3690 GROVES ROAD, COLUMBUS, OH 43232 (NAICS 562920). OSHA activity number 339942963.

Watch Novotec Recycling — free Get an email when a new federal OSHA severe-injury report for Novotec Recycling is published. One employer, no account, unsubscribe in one click.
Establishment
NOVOTEC RECYCLING
Site address
3690 GROVES ROAD
City
COLUMBUS
State
OH
ZIP
43232
Mailing
3690 GROVES ROAD, COLUMBUS, OH 43232
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562920
Employees
60
Ownership type
A

3 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3060.00 · Current $1530.00 Reduced
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.   a. At the workplace in the Main Production area, circuit breaker panel "D", a 120/240 volt circuit breaker panel, was not legibly marked so as to indicate the purpose of each overcurrent device.  Employees were exposed to electrical hazards while turning lights on and off from the panel.
Recent events (2)
  • — I (S) $1530
  • — Z (S) $3060

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3060.00 · Current $1530.00 Reduced
29 CFR 1910.304(g)(5):   Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.  a. At the workplace in the production area, employees were exposed to an ungrounded 120 volt industrial fan.  The fan's grounding pin was removed/missing causing the fans' body to carry current.
Recent events (2)
  • — I (S) $1530
  • — Z (S) $3060

1910.305 B01 II

Serious Gravity 5 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $3825.00 · Current $1913.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.   a. At the workplace in the Main Production area, circuit breaker panel "D", a 120/240 volt circuit breaker panel, had a knockout hole on it's left front facing side that was not sealed.   b. At the workplace in the Main Production area, circuit breaker panel "D", a 120/240 volt circuit breaker panel, had a breaker missing on it's right side branch.
Recent events (2)
  • — I (S) $1912.5
  • — Z (S) $3825

KENWORTH