Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: EXPERIENCED BRICKLAYERS, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EXPERIENCED BRICKLAYERS, INC in 215-225 W. ONTARIO STREET, CHICAGO, IL 60610 (NAICS 238140). OSHA activity number 340079417.

Watch Experienced Bricklayers, INC — free Get an email when a new federal OSHA severe-injury report for Experienced Bricklayers, INC is published. One employer, no account, unsubscribe in one click.
Site address
215-225 W. ONTARIO STREET
City
CHICAGO
State
IL
ZIP
60610
Mailing
8832 FORESTVIEW ROAD - APT. 2, EVANSTON, IL 60203
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238140
Employees
3
Ownership type
A

4 citations on file for this inspection.

1926.404 B01 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
29 CFR 1926.404(b)(1)(i): General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors:  a) On or about November 12, 2014 - at a jobsite located at 215-225 W. Ontario Street, Chicago, IL. - employees using a temporary electrical outlet box to power tools and equipment were not using ground fault circuit interrupters or did not have an assured equipment grounding program, thereby exposing the employees to electrical shocks.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1926.403 B02

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $0.00 Reduced
29 CFR 1926.403(b)(2): Installation and use. Listed, labeled, or certified equipment shall be installed and used in accordance with instructions included in the listing, labeling, or certification:  a) On or about November 12, 2014 - at a jobsite located at 215-225 W. Ontario Avenue, Chicago, IL. - the employer did not ensure that the temporary electrical wiring on the jobsite was free from recognized hazards, in that an electrical box made to be attached to a structure was laying on the floor, thereby exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2000

1926.405 A02 II B

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(B):  Runs of open conductors shall be located where the conductors will not be subject to physical damage, and the conductors shall be fastened at intervals not exceeding 10 feet (3.05 m). No branch-circuit conductors shall be laid on the floor. Each branch circuit that supplies receptacles or fixed equipment shall contain a separate  equipment grounding conductor if the branch circuit is run as open conductors:  a) On or about November 12, 2014 - at a jobsite located at 215-225 W. Ontario Street, Chicago, IL. - the branch circuit conductors used to power tools and equipment were laying on the floor and exposed to damage, thereby exposing the employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 A02 II C

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.405(a)(2)(ii)(C): Receptacles shall be of the grounding type. Unless installed in a complete metallic raceway, each branch circuit shall contain a separate equipment grounding conductor, and all receptacles shall be electrically connected to the grounding conductor. Receptacles for uses other than temporary lighting shall not be installed on branch circuits which supply temporary lighting. Receptacles shall not be connected to the same ungrounded conductor of multiwire circuits which supply temporary lighting:  a) On or about November 12, 2014 - at a jobsite located at 215-225 W. Ontario Street, Chicago, IL. - the branch circuit used to power tools and equipment was not provided with a grounding conductor, thereby exposing the employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View EXPERIENCED BRICKLAYERS, INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340079417.