Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,913,242Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: PRECISION METAL FINISHING, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PRECISION METAL FINISHING, INC. in 7726 MCKINLEY AVE, MOBILE, AL 36608 (NAICS 332813). OSHA activity number 340125012.

Watch Precision Metal Finishing, INC. — free Get an email when a new federal OSHA severe-injury report for Precision Metal Finishing, INC. is published. One employer, no account, unsubscribe in one click.
Site address
7726 MCKINLEY AVE
City
MOBILE
State
AL
ZIP
36608
Mailing
7726 MCKINLEY AVE, MOBILE, AL 36608
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
3
Ownership type
A

9 citations on file for this inspection.

1910.305 B02 I

Serious Gravity 5 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1300.00 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a) Aristo Craft Power Buffer / Buffer Station #2; on or about December 9, 2014 and at times prior, employees were exposed to an electrical shock hazard in that employees were allowed to operate the buffer where the junction box was not provided with a cover, faceplate or canopy.  b) Siemens Buffer / Buffer Station #4; on or about December 9, 2014 and at times prior, employees were exposed to an electrical shock hazard in that employees were allowed to operate the buffer where the junction box was not provided with a cover, faceplate or canopy.
Recent events (2)
  • — I (S) $1300
  • — Z (S) $2000

1910.305 G02 II

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap:  a) Electrical Plate Station / Dip Tank #1 (Nickel Plate); on or about December 9, 2014 and at times prior, employees were exposed to electrical shock hazards in that employees were allowed to walk and work around an ungrounded and unguarded fixture cord that had been spliced and capped with wire nuts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 E01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:  a) Electrical Plate Station / Dip Tank #1 (Nickel Plate); on or about December 9, 2014 and at times prior, employees were exposed to electrical shock hazards in that employees were allowed to walk and work around a metal electrical junction box showing signs of damage, that was not designed to prevent moisture from accumulating within the enclosure.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a) Electrical Plate Station / Dip Tank #1 (Nickel Plate); on or about December 9, 2014 and at times prior, employees were exposed to electrical shock hazards in that employees were allowed to walk and work around junction boxes that did not have covers installed leaving the wires exposed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 D01

Serious Gravity 5 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1300.00 Reduced
29 CFR 1910.219(d)(1): Guarding. Pulleys, any parts of which are seven (7) feet or less from the floor or working platform, shall be guarded in accordance with the standards specified in paragraphs (m) and (o) of this section. Pulleys serving as balance wheels (e.g., punch presses) on which the point of contact between belt and pulley is more than six feet six inches (6 ft. 6 in.) from the floor or platform may be guarded with a disk covering the spokes.   a)  No Name / Buffing Station #1; on or about December 9, 2014 and at times prior, the employer exposed the employer to ingoing nip point hazards in that employees were allowed to operate the Buffer where belt and pulleys created ingoing nip point hazards and were not guarded by but not limited to barrier guards or other safety devices.  b)  Siemens Buffer / Buffing Station #4; on or about December 9, 2014 and at times prior, the employer exposed the employer to ingoing nip point hazards in that employees were allowed to operate the Siemens Buffer where belt and pulleys created ingoing nip point hazards and were not guarded by but not limited to barrier guards or other safety devices.
Recent events (2)
  • — I (S) $1300
  • — Z (S) $2000

1910.219 C02 I

Serious Gravity 1 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.219(c)(2)(i): All exposed part(s) of horizontal shafting seven (7) feet or less from floor or working platform were not protected by stationary casing(s) enclosing shafting completely or by trough(s) enclosing sides and top or sides and bottom of shafting:  a)  Buffing Station #1; on or about December 9, 2014 and at times prior, the employer exposed the employees to amputation hazards in that he allowed his employees to work within two feet of tan unguarded rotating shaft.  b) Aristo Craft Power Buffer / Buffing Station #2; on or about December 9, 2014 and at times prior, the employer exposed the employees to amputation hazards in that he allowed his employees to work within two feet of tan unguarded rotating shaft.  c)  Siemens Buffer / Buffing Station #4; on or about December 9, 2014 and at times prior, the employer exposed the employees to amputation hazards in that he allowed his employees to work within two feet of tan unguarded rotating shaft.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.219 C04 I

Serious Gravity 10 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.219(c)(4)(i): Unguarded rotating shaft ends projected more than one-half the diameter of the shaft:  a)  Buffing Station #1; on or about December 9, 2014 and at times prior, the employer exposed his employees to fracture and amputation hazards in that employees were allowed to operate the Buffer where the unguarded shaft ends protruded more than one-half the diameter of the shaft.  b) Aristo Craft Power Buffer / Buffing Station #2; on or about December 9, 2014 and at times prior, the employer exposed his employees to fracture and amputation hazards in that employees were allowed to operate the Buffer where the unguarded shaft ends protruded more than one-half the diameter of the shaft.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.151 C

Serious Gravity 5 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1300.00 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  a)  Platting Area:  On or about December 9, 2014 and at times prior; employees working in the platting area were exposed to corrosive materials without being provided with a functional eye wash station.
Recent events (2)
  • — I (S) $1300
  • — Z (S) $2000

1910.212 A05

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level:  a)  Electrical Plate Station / Dip Tank #1 (Nickel Plate); on or about December 9, 2014 and at times prior, employees were exposed to struck by hazards by a fan blade attached to a small electric motor that was not provided with a guard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View PRECISION METAL FINISHING, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340125012.