SAIPAN, MP —
OSHA Inspection: HOTEL SUN PALACE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of HOTEL SUN PALACE in BWUGHOS STREET SUSUPE VILLAGE, SAIPAN, MP 96950 (NAICS 721110). OSHA activity number 340160076.
Where did this inspection happen?
- Establishment
- HOTEL SUN PALACE
- Site address
- BWUGHOS STREET SUSUPE VILLAGE
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- PO BOX 500920, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 10
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Penalty
- Initial $1600.00 · Current $733.00 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On January 26, 2015, outside the laundry room, a metal electrical receptacle box designed to be installed inside of a wall was used on the end of an extension cord powering a portable saw.
Recent events (2)
- — I (S) $733
- — Z (S) $1600
1910.305 G01 IV A
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On January 26, 2015, in the laundry room, a cord was hardwired into a 220 volt receptacle box to provide power for a portable saw outside of the laundry room.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Penalty
- Initial $1200.00 · Current $733.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) On January 26, 2015, an electrical outlet box located inside the laundry room above the washing machine, did not have their faceplates installed exposing the wire connections. b) On January 26, 2015, an electrical outlet box located inside the outdoor kitchen inside the screen window and above the sink, did not have their faceplates installed exposing the wire connections.
Recent events (2)
- — I (S) $733
- — Z (S) $1200
1910.305 E02
- Issued
- Penalty
- Initial $1600.00 · Current $733.00 Reduced
General-duty citation text
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures: a) On January 26, 2015, inside the outside kitchen near the sink, the employer installed an overhead light switch without an enclosure and using connections made using electrical tape exposing employees to electrical and fire hazards.
Recent events (2)
- — I (S) $733
- — Z (S) $1600
More inspections in this industry (NAICS 721110)
LAS VEGAS, NV—2026-07-13
THE BERKLEY LAS VEGAS
LYNCHBURG, VA—2026-07-10
RIVERFRONT HOSPITALITY LLC
INCLINE VILLAGE, NV—2026-07-09
SHANTI RAHM LLC.
INCLINE VILLAGE, NV—2026-07-09
SHANTI RAHM LLC.
ISELIN, NJ—2026-07-09
DELTA HOTELS WOODBRIDGE
More inspections in MP
SAIPAN, MP—2025-05-15
PARAGON CORP.
SAIPAN, MP—2025-05-14
WINZY CORPORATION
SAIPAN, MP—2025-05-14
HONG YE RENTAL & CONSTRUCTION, LTD.
SAIPAN, MP—2025-05-14
GU LI QIANG
SAIPAN, MP—2025-05-14
GENESIS ENTERPRISES, LLC
Source